SK 54xE – Users Manual for Frequency Inverters
"Ø" =
Parameter has no significance
"√" =
Setting of the parameter is relevant
Group
Parameter
P300
P301
P310 ... P320
P312, P313, P315, P316
P330 ... P333
P334
1)
=
For V/f characteristic curve: precise matching of the parameter is important.
2)
=
For V/f characteristic curves: typical setting "0"
Pos: 115.7 /Anleitungen/Elektronik/FU und Starter/4. Inbetriebnahme/Auswahl Motorregelverfahren/Inbetriebnahmeschritte Motorregelung [SK 2xxE, SK 5xxE] @ 6\mod_1421077959056_388.docx @ 198572 @ 3 @ 1
4.2.3
Motor control commissioning steps
The most important commissioning steps are mentioned below in their ideal order. Correct assignment
of the inverter / motor and the mains voltage is assumed. Detailed information, especially for
optimisation of the current, speed and position control of asynchronous motors is described in the
guide "Control optimisation" (AG 0100). Detailed commissioning and optimisation information for
PMSM in CFC closed loop operation can be found in the "Drive optimisation" guideline (AG 0101).
Please contact our Technical Support.
1. Carry out the motor connection as usual (note ∆ / Y !). Connect the encoder, if present
2. Connect the mains supply.
3. Carry out the factory setting (P523)
4. Select the basic motor from the motor list (P200) (ASM types are at the beginning of the list, PMSM
types are at the end, designated by their type (e.g. ...80T...))
5. Check the motor data (P201 ... P209) and compare with the type plate / motor data sheet
6. Measure the stator resistance (P220) P208, P241[-01] are measured, P241[-02] is calculated.
(Note: is an SPMSM is used, P241[-02] must be overwritten with the value from P241[-01])
7. Rotary encoder: Check the settings (P301, P735)
8. Select the operating mode (P300)
9. with PMSM only:
a. EMF voltage (P240) motor type plate / motor data sheet
b. Determine / set reluctance angle (P243) (not required with NORD motors)
c. Peak current (P244) motor data sheet
d. Only for PMSMs in VFC mode:
determine (P245), (P247)
e. Determine (P246)
10. Determine / adjust the current control (P312 – P316)
11. Determine / adjust the speed control P310, P311)
12. PMSM only:
a. Select the control method (P330)
b. Make the settings for the starting behaviour (P331 ... P333)
c. Make the settings for the 0 pulse of the encoder P334 ... P335)
Pos: 116 /Anleitungen/Elektronik/FU und Starter/4. Inbetriebnahme/SK 500E/4.2 Minimalkonfiguration der Steueranschlüsse @ 0\mod_1327569977746_388.docx @ 7219 @ 255 @ 1
88
"-" =
Leave the parameter in the factory setting
"!" =
Setting of the parameter is important
Operating mode
VFC open-loop
CFC open-loop
ASMs
PMSMs
ASMs
√
√
Ø
Ø
Ø
Ø
Ø
Ø
√
-
Ø
Ø
CFC closed-loop
PMSMs
ASMs
√
√
√
Ø
Ø
!
√
√
√
√
-
-
√
-
-
Ø
Ø
-
BU 0505 EN-3021
PMSMs
√
!
√
√
√
√