INTRODUCTION
This instruction sheet provides you with the information required to safely own
and operate your product. Retain these instructions for future reference.
The product you have purchased is of the highest quality workmanship and
material, and has been engineered to give you long and reliable service. This
product has been carefully tested, inspected, and packaged to ensure safe
delivery and operation. Please examine your item(s) carefully to ensure that no
damage occurred during shipment. If damage has occurred, please contact the
place of purchase. They will assist you in replacement or repair, if required.
READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING
TO INSTALL, OPERATE, OR SERVICE YOUR PRODUCT. KNOW THE
PRODUCT'S APPLICATION, LIMITATIONS, AND POTENTIAL HAZARDS.
PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY
INFORMATION. FAILURE TO COMPLY WITH THESE INSTRUCTIONS
COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE!
DESCRIPTION
Little Giant submersible 16EH and 16S series pumps are recommended for use
in basins or lift stations and suitable for pumping sewage, effluent, wastewater
and other non-explosive, non-corrosive liquids. The S Series Sewage Pumps
have 2" spherical solids handling capability. The EH Series Effluent Pumps have
3/4" spherical solids handling capability.
Little Giant offers a complete line of float switches and liquid level control systems
for automatic operation along with a complete line of alarms, basins, covers, and
check valves.
SPECIFICATIONS
Discharge:
16EH – 2", 16S – 3"
Handling Capabilities: EH Series – 3/4" spherical solids
S Series – 2" spherical solids
Housing:
Cast Iron
Volute:
Cast Iron
Impeller:
Non-clog cast iron, with pressure relief vanes
Motor:
3 phase, 3450 RPM (EH Series)
3 phase, 1725 RPM (S Series)
Hardware:
300 Series stainless steel
Bearing:
Ball
Shaft Seal:
Mechanical, spring loaded, rotating carbon with Nitrile
boot and stationary ceramic seat, with secondary Nitrile
exclusion seal
Power Cord:
18AWG, 4-conductor, copper-stranded
Figure 1
16EH-CIM
16S-CIM
3-PHASE
Cooling:
The motor housing contains a cooling oil to provide
cooling for the motor and to lubricate bearings and
seals. These pumps are capable of operating with the
motor housing partially exposed for extended periods
of time, providing sufficient motor cooling and bearing
lubrication, however, for the best cooling and longest
motor life, the liquid being pumped should normally
be above the top of the cast iron motor housing.
SAFETY GUIDELINES
WARNING: RISK OF ELECTRIC SHOCK. THIS PUMP IS SUPPLIED WITH A
GROUNDING CONDUCTOR. TO REDUCE THE RISK OF ELECTRIC SHOCK,
BE CERTAIN THAT IT IS CONNECTED TO A PROPER ELECTRICAL GROUND.
DO NOT REMOVE CORD OR STRAIN RELIEF, DO NOT CONNECT CONDUIT
TO PUMP. THIS PUMP MUST BE INSTALLED BY QUALIFIED PERSONNEL.
1. Read all instructions and safety guidelines thoroughly. Failure to follow the
guidelines and the instructions could result in serious bodily injury and/or
property damage.
2. DO NOT USE TO PUMP FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS
GASOLINE, FUEL OIL, KEROSENE, ETC. FAILURE TO FOLLOW THIS
WARNING CAN RESULT IN PERSONAL INJURY AND/OR PROPERTY
DAMAGE.
Figure 2
1

Advertisement

loading

Summary of Contents for Little Giant 16EH-CIM

  • Page 1 2" spherical solids handling capability. The EH Series Effluent Pumps have 3/4" spherical solids handling capability. Little Giant offers a complete line of float switches and liquid level control systems for automatic operation along with a complete line of alarms, basins, covers, and check valves.
  • Page 2 If pump does not operate properly, consult the Troubleshooting Chart. If trouble cannot be located with these steps shown, consult your pump dealer or take pump to a Little Giant authorized service center. 200-208 CAUTION: When working on pump or switch, always unplug pump power cord in addition to removing fuse or shutting off circuit breaker before working The pump will run continuously when wired directly into an electrical outlet.
  • Page 3 Figure 4 OIL AND SEALED AT THE FACTORY. REMOVAL OF THESE SOCKET HEAD CAP SCREWS BY ANYONE OTHER THAN AN AUTHORIZED LITTLE GIANT SERVICE CENTER WILL BREAK THIS SEAL AND VOID THE WARRANTY. 1. Remove the 4 screws (item 12 on parts list) that hold the volute to the motor housing.
  • Page 4 140°F with up to 2" spherical solids handling ability. shall be the replacement and/or repair by the manufacturer of the product as Each of the above noted Little Giant products is guaranteed to be in perfect described above. Neither seller nor the manufacturer shall be liable for any condition when it leaves our factory.