Rack Mounting A Single Ied And Test Switch Rtxp - ABB Relion 650 Series Installation Manual

Intelligent electronic device
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 514 013-UEN -
4.3.3.3
650 series
Installation Manual
1
GUID-77659F5C-692A-4A14-BE37-623C09FCBF0C V1 EN
Figure 10:
Two rack mounted IEDs side by side
A 224 mm + 12 mm with ring-lug connector 1 Screws
B 25.5 mm
C 482.6 mm (19")
D 13 mm
E 265.9 mm (6U)
See that the lower venting holes in the IED is not obstructed.

Rack mounting a single IED and test switch RTXP

1.
Attach the mounting bracket to the left side of the IED using the required screws.
2.
Tighten the screws
3.
Remove the four plastic plugs from the right side of the IED and attach the
mounting bracket securely using the required screws.
4.
Tighten the screws.
5.
Mount the IED with the rack mounting panels to the 19" rack.
6.
Tighten the fixing screws.
7.
Install the RTXP 8, 18 or 24 test switch.
8.
Attach the front cover over to the test switch.
Section 4
Mounting
21

Advertisement

Table of Contents
loading

Table of Contents