10
Short circuit:
- on the secondary circuit of the pulse transformer.
- on the heating element.
- on the twisted cable.
11
Heating activated in error;
this error indicates a likely fault in the power adjustment element. It can
activate in the event of high inductive pulses on the power supply.
14
Memory not valid on the temperature controller;
load a basic configuration on the temperature controller and proceed with a
new configuration.
15
Memory not valid on the temperature controller;
repair the temperature controller.
16
Internal fault;
repair the temperature controller.
Configuration
Configuration of the parameters can be executed via:
Remote mode RS485: the configurations can be executed through commands sent via
•
interface EIA/TIA485.
Internal mode via the numerical display: the configurations are executed directly using the
•
associated keys.
With serial bus connection
In this mode, configuration is executed using the commands sent via the EIA/TIA485 interface by
a PLC or PC remote device. The communication protocol manual is separate and available on
request.
With numerical display
Once the equipment starts, it works in operating mode displaying the temperature read on the
heating element.
Press the
cfg
key on the keypad to display the first basic parameter or
return to the temperature display.
0 0
Basic parameters
The value is displayed that is currently set of the pre-heating temperature on the top
050
display and
key to go to the next parameter or press the
≡
p h
between the minimum of 50° and the maximum which is set in configuration
key activates the value or saves it in the temperature controller memory.
15
key twice to display
≡
on the bottom display. If you do not want to edit the value, press the
PH
. The lower display shows
CFG
and
. Press the
00
again if you want to
≡
keys to edit the value
13
. The