AMC-360-IREP 0-100% LEL Methane Sensor/Transmitter 2 PRODUCT INFORMATION 2.1 TRANSMITTER Transmitter Unit Order Number ……………..……………………. Transmitter Part Number……………..…..…………...…………… Transmitter Serial Number ………………………………………… Sensor Part Number/WARRANTY………………..………………. Sensor Serial Number …………………………….……………….. Power Supply Requirement …………………….…………………. 12 to 26 VDC @ _____ mA Signal Output Load ……………………………..…………………..
3 PRODUCT DESCRIPTION 3.1 GENERAL DESCRIPTION The AMC-360-IREP sensor/transmitter unit is designed to provide continuous, reliable surveillance of surrounding air for up to 100% by LEL methane. Used with this sensor, the unit provides a 4 to 20 mA, variable current signal which is proportional to the gas concentration currently detected.
AMC-360-IREP 0-100% LEL Methane Sensor/Transmitter 3.2 HOUSING OPTIONS The AMC-360-IREP series transmitter units are available in the following housing (see FIGURE 1). The explosion-proof housing is also available with a corrosion resistant finish. • Explosion-Proof (rated for Class I, Groups B, C, D)
AMC-360-IREP 0-100% LEL Methane Sensor/Transmitter 4 INSTALLATION 4.1 LOCATION AND MOUNTING Mount the sensor/transmitter unit on a solid, non-vibrating surface or structure in an area where the local concentration of gas is unaffected by the presence of ventilation systems and away from sources of interference gases.
See Figure 4 to select cable length and wire gauge according to supply voltage. Run cable through steel conduit for best signal transmission and maximum noise rejection. 4.2.1 TRANSMITTER INTERFACE TO COMPUTER, DATALOGGER OR NON-AMC SYSTEM All Armstrong transmitter/sensor units can be interfaced with computer terminals or dataloggers through Analog-to-Digital converters.
5 OPERATION AND CALIBRATION 5.1 OPERATION The AMC-360-IREP series transmitter/sensor unit is factory calibrated for the gas listed in section 3.1 GENERAL DESCRIPTION. The unit should not need recalibration when first installed and powered up, but a test for correct operation is recommended. All testing should be done after a stabilization period of 20 seconds.
AMC-360-IREP 0-100% LEL Methane Sensor/Transmitter 5.2.2 TRANSMITTER CALIBRATION / VERIFICATION SET-UP PROCEDURE The calibration procedure may cause the monitoring equipment to give a false alarm, therefore appropriate precautions should be taken. Refer to Figure 5 for the following procedure. 1. Remove cover from transmitter housing 2.
AMC-360-IREP 0-100% LEL Methane Sensor/Transmitter 6 PREVENTIVE MAINTENANCE 6.1 GENERAL The transmitter/sensor unit should be brushed or wiped clean once a year or more, of any dust or dirt which settles on it, depending on the accumulation. The unit SHOULD NOT be submerged in water or other liquids.