1.2 PRODUCT RETURN All products returned for warranty or service should be shipped by prepaid freight and will be accepted only with RMA or repair number issued by AMC. All products returned to the client will be shipped by freight collect.
SIR_manual_rev_X as the filename on the front page. The filename specified for this manual on the front page is 3305405F. Sensor 1 Sensor 2 DIFFERENT CONNECTORS TRANSMITTER TRANSMITTER TO MONITOR TO MONITOR SigV SigV LED1 LED1 POWER POWER Figure 2-1 AMC-SIR Refrigerant Gas sensor 2 vs sensor 1...
AMC-SIR Refrigerant Gas Sensor/Transmitter 2.2 SENSOR/TRANSMITTER MODULE Sensor/transmitter unit order number. ………... Sensor/transmitter serial number...……………. 14 to 28VDC Power Supply Requirement…………………….. 70mA average, 140mA max Current Requirement……………………...…….. Operating Temperature ………………………… -20° to +40° C Relative Humidity ……………………………….. 0 to 95% RH, non-condensing Signal Linearity…………………………………...
AMC-SIR Refrigerant Gas Sensor/Transmitter 3 PRODUCT DESCRIPTION The AMC-SIR Refrigerant Gas sensor/transmitter unit is designed to provide continuous, reliable surveillance of surrounding air for the target gas listed in the Factory Calibration (Section 2.3). Based on the physical measurement method of infrared absorption, it provides the best technique for reliable, precise measurements and selectivity.
4.1 LOCATION AND MOUNTING Mount the AMC-SIR Refrigerant Gas sensor/transmitter on a solid, non-vibrating surface or structure in an area where the ambient concentration of gas is not directly affected by the presence of clean air supply, ventilation systems, or blockage by surrounding articles and sources of interference gas or contaminants.
AMC-SIR Refrigerant Gas Sensor/Transmitter 4.2 WIRING The AMC-SIR Refrigerant Gas sensor/transmitter was designed to operate with a power supply voltage range of 14V to 28VDC. It can be interconnected to a suitable Armstrong monitor panel or be powered from a stable 14-28VDC power source, with its 4-20mA signal interconnected to a suitable measuring device.
Figure 4-3 Jumper (JP3) installed 4.2.1.2 TRANSMITTER TO MONITOR WIRING When connecting to an AMC Monitor, the AMC-SIR Refrigerant Gas sensor/transmitter is wired with a 3-conductor shielded cable. Fig. 4-4 shows the connection between the AMC-SIR Refrigerant Gas sensor/transmitter and an AMC Monitor. In this configuration, power is provided via the Monitor.
To accomplish this, a high-precision resistor must be connected to the current input of the non AMC monitor as a shunt. See Fig. 4-6. The resultant voltage drop across the resistor then linearly reflects the concentration value of the measured gas.
Page 12
TRANSMITTER HOUSING REMOVED FOR CLARITY TRANSMITTER TO MONITOR SHIELD NON-AMC SigV MONITOR LED1 POWER CHASSIS GND NOTE: ALL WIRING MUST PASS THROUGH CONDUIT OPENING LOCATED AT THE BOTTOM OF ENCLOSURE. REFER TO FIGURE 4-1 Figure 4-6 Transmitter to Non-AMC Monitor with shunt resistor...
2 minutes, in a gas-free environment. The sensor signal can fluctuate during the warm-up period. When the boot phase is finished, and when all test routines have properly finished, the AMC- SIR Refrigerant Gas sensor/transmitter automatically switches to normal operating mode and provides a signal output proportional to the gas concentration.
AMC-SIR Refrigerant Gas Sensor/Transmitter 4.3 CABLE SELECTION The following section details the cable selection needed to ensure proper operation of the AMC- SIR Refrigerant Gas sensor/transmitter. The figure below is an aid for cable selection. A 3-conductor shielded cable is employed for interconnection.
A calibration jack plug type test lead for the above meter (provided by AMC) Zero & Span gases for use with a 0.5lpm flow regulator (contact AMC for information) Cal Adapter, P/N: AMC-FL1 or AMC-C1-FL1 for calibration kit 5.2 CALIBRATION PROCEDURE...
The zero point should be checked with zero gas. Gas should be applied at 0.5lpm using the AMC-FL1 calibration adapter, as shown in Figure 5-1.Once the sensor has been completely purged, the output measured at the cal jack should be between 3.9 - 4.1mA. If the measured value is: ...
1. Disconnect power at the plug-in TB-2 terminal. Ensure both JP2 and JP3 jumpers are not installed, then re-connect power to AMC-SIR. Wait for Sensor to finish boot up stage (3 minutes after power up) before applying the zero gas as above and make sure that the sensor has been completely purged.
6 MAINTENANCE 6.1 GENERAL The AMC-SIR Refrigerant Gas sensor/transmitter unit should be brushed or wiped as required, depending on the rate of accumulation of any dust or dirt. To avoid sensor damage, the unit MUST NOT be submerged in any liquids.