Download Print this page

Siemens SIPLUS HCS Compact Operating Instructions page 4

Hide thumbs Also See for SIPLUS HCS:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 3
Technical specifications
Temperature measuring inputs
Number of analog inputs with
2-wire technology
Number of analog inputs with
4-wire technology
Type of connection
Physical measuring principle
Measuring accuracy:
A/D conversion time at
analog input
Sensor circuit, typical
Isolation between channels
Impulse withstand voltage of
inputs, maximum
Temperature drift per °C,
typical
Temperature offset per K,
maximum
Temperature measurement
deviation per K, maximum
Connectable sensors
Temperature measuring
range with Pt 100 according
to IEC 60751
Temperature measuring
range with Pt 1000 according
to IEC 60751
Temperature measuring
range for type J thermocouple
Temperature measuring
range for type K
thermocouple
4
4
2
2-wire and 4-wire
technology
Sigma Delta
± 1 K
150 ms
210 μA
No
15 V
0.05 %/°C
0.1 K/K
11.5 ppm
0...410 °C
0...850 °C
0...650 °C
0...440 °C
Temperature measuring
range for type L
thermocouple
Analog inputs - current
Number of analog inputs
Current measuring range
Relative measuring accuracy
referred to measured current
value
Ambient conditions
Ambient temperature during
operation
Ambient temperature during
storage and transport
Relative air humidity during
operation and storage
Degree of pollution
Installation altitude above sea
level, max.
Mechanical specifications
Weight
Degree of protection
Dimensions (W x H x D)
Technical Assistance
Telephone: +49 (0) 911-895-7222 (8°° - 17°° CET)
Email: technical-assistance@siemens.com
Internet: www.siemens.com/automation/support-request
Additional documentation
You will find more detailed information in Siemens Industry
Online Support
(http://support.automation.siemens.com/WW/view/en/10807
371/133300).
0...640 °C
4
0...20 mA
0.5%
0 °C to 55 °C
-25 ℃ to +70℃
95 % at 25 °C, decreasing
linearly to 50 % at 50 °C
2
2000 m
Approx. 0.15 kg
IP20
27 mm x 141 mm x 110
mm
HCS I/O4000 Temperature
A5E36313298A/001, 09/2015

Advertisement

loading

This manual is also suitable for:

Hcs pm4000 temperatur