INDOOR INSTALLATION AND VENTING

POSITIVE AND NEGATIVE PRESSURE VENTING SySTEMS
The heater is designed such that it may be vented using either a negative-pressure or a positive-pressure
venting system. The appropriate system of venting for a particular site will depend on many factors such as
vent termination needs (horizontal/vertical), and the cost of venting system. Table 3 lists the indoor venting
kits available and the limitations of each system.
Indoor Vent Kit Part
Number
UHXNEGVT11501
UHXNEGVT12001
Indoor Vent Adapter Kit,
UHXNEGVT12501
Negative Pressure,
UHXNEGVT13001
Vertical Venting
Applications
UHXNEGVT13501
UHXNEGVT14001
UHXPOSHZ11501
UHXPOSHZ12001
Indoor Vent Adapter Kit,
UHXPOSHZ12501
Positive Pressure,
Horizontal or Vertical
UHXPOSHZ13001
Venting Applications
UHXPOSHZ13501
UHXPOSHZ14001

CLEARANCES

The heater must be installed such that the installation and
service clearances from combustible materials shown in Table
4 are maintained. This heater may be installed on combustible
floors. Do not install heater in a closet.

AIR SUPPLy

Indoor installations and outdoor shelters (confined spaces)
must be provided with adequate combustion and ventilation air
vents to assure proper heater operation. These vents must be
sized according to the requirements stated in paragraph A or B below (whichever applies to the installation).
These vents must never be obstructed when heater is in operation.
When air blowers are used in spa/hot tub installations and are located in proximity to the heater, caution
must be observed to ensure sufficient combustion air is available to the heater for proper combustion. A separate
blower air duct is recommended.
Indoor Vent Kits and Limitations of Venting Systems
For Use With
Description
Heater
Models
H150FD
H200FD
H250FD
H300FD
H350FD
H400FD
H150FD
H200FD
H250FD
H300FD
H350FD
H400FD
Table 3
Vent Pipe Limitations
50 ft max vetical height,
25 ft max horizontal length
(horizontal length cannot
exceed 1/2 of vertical height),
3 elbows max
50 ft max with 1 elbow,
40 ft max with 2 elbows,
or 30 ft max with 3 elbows
(horizontal or vertical)
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Pomona, CA Clemmons, NC Nashville, TN
Tel: 908-351-5400
Vent Pipe
Material
Single or Double
Wall Galvanized
Non-Sealed
Vent Pipe
Single or Double
Wall Stainless
Steel Sealed
Vent Pipe
Table 4
Indoor Installation Clearances
Heater Panel
Top
Front
Back
Water Connection Side
Side Opposite Water
Connection
www.haywardpool.com
13
Vent
Termination
Requirement
Vertical Only,
Termination Above
Roof of House/
Building
Horizontal or
Vertical, Termina-
tion Immediately
Outside Wall of
House/Building
Required Clearance
36 inches
24 inches
6 inches
12 inches
6 inches