APPLY WRENCH
FROM TOP OR
BOTTOM OF GAS
CONTROL TO
EITHER SHADED AREA
GAS CONTROL
FITTING BREAKS OFF AND CLINCHES
TUBING AS NUT IS TIGHTENED.
Fig. 8. Always use new compression fitting.
Connect Thermocouple
If a supplementary limit or energy cutoff (ECO) are used,
insert the ECO connector (order Part No. 393200Ñ1) as
shown in Fig. 9, then connect thermocouple lead. If not,
insert thermocouple lead directly. This is an electrical
connection and must be clean and dry. Never use pipe
compound. Tighten only 1/4 turn beyond finger tight to
give good electrical continuity. Do not overtighten.
WHEN FLANGE IS NOT USED
Fig. 7. Proper use of wrench on gas control.
TIGHTEN NUT ONE TURN
BEYOND FINGER TIGHT.
TO PILOT
BURNER
M3076A
ECO
CONNECTOR
1
THIS IS AN ELECTRICAL CONECTION AND MUST BE
CLEAN AND DRY. DO NOT USE PIPE COMPOUND.
M3095
Fig. 9. Installing thermocouple and optional
ECO connector to the power unit.
7
V8200 COMBINATION GAS CONTROLS
WHEN FLANGE IS USED
APPLY WRENCH
TO FLANGE ONLY
M3079
THERMOCOUPLE
LEAD
1
68-0045—3