Honeywell V8200 Manual page 3

Combination gas controls

Advertisement

Capacity:
3
3
130 feet
/hour (4.2 meter
3
1000 Btu/feet
, 0.64 specific gravity natural gas at 1 inch
water column pressure drop (37.3 MJ/meter
gravity natural gas as 0.25 kPa pressure drop).
Maximum regulated capacity is 200 feet
3
(5.7 meter
/hour).
Minimum regulated capacity is 20 feet
3
(0.6 meter
/hour).
Use conversion factors in Table 2 to convert to capacities for
other gases.
Table 2. Gas Capacity Conversion Factors.
Specific
Gas
Gravity
Manufactured
0.60
Mixed
0.70
Propane
1.53
Body Pattern:
Straight-through with 1/2 inch inlet and outlet.
Adapters available for 3/8, 1/2 and 3/4 inch straight and angle
connection. See Table 3.
NOTE: Adapters may be field installed or factory installed.
Reference individual OS number specifications for
availability of factory installed. Reference individual
OS number specifications for availability of factory
installed adapters.
Pilot Gas Outlet: Compression fitting for 1/4 inch OD tubing.
Pressure Tapping: Inlet and outlet pressure taps included.
Taps accessible from top of gas control. Taps are 1/8 inch
NPT with plug containing recess for 3/16 inch Allen wrench.
Table 3. Adapter (Flange) Part Numbers.
3/8 in.
Straight
390427B
Bushing (1)
390427C
Bushings (2)
393690-2
a
Angle
Flange Kit
a
A right-angle flange cannot be used on the inlet end of the
ECO Adapter is used.
NOTE: Flange Kits include one flange with attached O-ring,
four mounting screws, 9/64 inch hex wrench and
instruction sheet.
/hour). Capacity is based on
3
, 0.64 specific
3
/hour
3
/hour
Multiply Listed
Capacity By
0.516
0.765
1.62
1/2 in.
3/4 in.
393690-6
393690-4
Flange Kit
Flange Kit
393690-3
393690-5
Flange Kit
Flange Kit
Pressure Rating: AGA rating 1/2 psi (3.5 kPa) inlet
pressure.
Pressure Regulation: See Table 1. Regulator adjustment
accessible from top of gas control.
Mounting: Can be mounted 0 to 90 degrees in any direction
from the upright position of the manual gas control knob,
including vertically.
Temperature Rating:
V8200A,C,H: 0°F to 175°F (-18°C to +79°C).
V8200M: -40°F to +175°F (-40°C to +79°C).
Dimensions: See Fig. 1.
Approvals:
American Gas Association: Design Certificate P-70-42A.
Canadian Gas Association: Design Certificate 1029-CC-6395
Series.
Australian Gas Association: 4214.
Underwriters Laboratories Incorporated Component
Recognized: File Number MH5323.
Optional Specifications: Convenience terminals.
Accessories:
Adapters, see Table 3.
393200-1 ECO Connector.
393691 Natural to LP Conversion Kit.
394588 LP to Natural Conversion Kit.
394349 9/64 inch hex tool for flange assembly screws.
4-1/8 (104)
M16284
Fig. 1. V8200 dimensions in in. (mm).
3
V8200 COMBINATION GAS CONTROLS
1/4 in. QUICK-
OPTIONAL
CONNECT
CONVENIENCE
TERMINALS
TERMINAL
3-5/8 (91)
SWING
RADIUS
1/2
(13)
1 (25)
1/2
(13)
1
(25)
2-11/16 (69)
3-1/2
(99)
MV
MV
1-11/16
(43)
68-0045—3