INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
FOR 45000 SERIES HEAT PUMPS

TABLE OF CONTENTS

I.
II.
III.
IV.
V.
VI.
VII.
These instructions are a general guide for installing the 45000 Series Coleman-Mach roof top Heat Pumps. For
specific Heat Pump details, it will be necessary to refer to ALL printed documents supplied with this unit.
These instructions are for the use of qualified individuals specially trained and experienced in installation of this type
equipment and related system components.
Installation and service personnel are required by some states to be licensed. PERSONS NOT QUALIFIED SHALL
NOT INSTALL NOR SERVICE THIS EQUIPMENT.
NOTE: The words "Shall" or "Must" indicate a requirement which is essential to satisfactory and safe product
performance. The words "Should" or "May" indicate a recommendation or advice which is not essential and not
required but which may be useful or helpful.
WARNING! - SHOCK HAZARD To prevent the possibility of severe personal injury or equipment damage due
to electrical shock, always be sure the electrical power source to the appliance is disconnected.
CAREFULLY FOLLOW ALL INSTRUCTIONS AND WARNINGS IN THIS BOOKLET TO
AVOID DAMAGE TO THE EQUIPMENT, PERSONAL INJURY OR FIRE.
WARNING! Improper installation may damage equipment, can create a hazard and will void the warranty.
The use of components not tested in accordance with these units will void the warranty, may make the equipment
in violation of state codes, may create a hazard and may ruin the equipment.
P/N: 1980-054
RV Products Division
2
2
2
2
2
4
4
6
6
IMPORTANT NOTICE
VIII.
IX.
i.
ii.
iii.
iv.
v.
vi.
X.
6
10
10
10
11
11
12
12
28
04-26-2016

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 45000 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Airxcel 45000 Series

  • Page 1: Table Of Contents

    Installing Ceiling Assembly (9600 Series) These instructions are a general guide for installing the 45000 Series Coleman-Mach roof top Heat Pumps. For specific Heat Pump details, it will be necessary to refer to ALL printed documents supplied with this unit.
  • Page 2: General Information

    It may be necessary to seal some of the old roof III. SELECTING AN INSTALLATION LOCATION vent mounting screw holes which may fall outside Your Airxcel, Inc. Heat Pump has been designed for use of the Heat Pump basepan gasket. primarily in recreational vehicles.
  • Page 3 Heat Pump through Airxcel’s 45000 series requires that the spacing from the the mounting opening and let hang. vehicle roof top to the interior ceiling be no less than 1”.
  • Page 4: Oem Top/Down Mounting

    ROUTING 115 VAC WIRING securely fasten the rooftop unit. Following Airxcel’s high voltage wiring specifications and all Confirm that the mounting hole area has been properly local and national electrical codes, route the roof top unit 115 prepared.
  • Page 5 REFER TO OEM DUCTING REQUIREMENTS FOR SUPPLY AND RETURN DUCTING INFORMATION. OEM DUCTING REQUIREMENT DOCUMENT IS AVAILABLE AT www.AIRXCEL.com. IT IS THE RESPONSIBILITY OF THE INSTALLER TO PROVIDE THE MEANS FOR SEGREGATION OF SUPPLY AND RETURN AIR. RETURN AIR SUPPLY AIR...
  • Page 6: Installing Optional Heater Accessory

    (See Figure 9). Tighten set screw to secure the assembly to prevent Airxcel, Inc. manufactures a wide range of roof top Heat movement. Replace the selector switch control knob Pumps which incorporate different product operation on the ceiling assembly with the knob provided with the features.
  • Page 7 FIGURE 9 FIGURE 10...
  • Page 8 ROOFTOP UNIT MOUNTING FRAME ROOF STRUCTURE DUCT COLLAR CEILING ASSEMBLY CHUTE FABRIC DUCT MATERIAL CEILING FILTERS ASSEMBLY SHROUD CONTROL KNOBS FIGURE 11 GRILLES...
  • Page 9 Apply today by filling out the application located on the back cover of this Installation and Operation Manual and mailing it in along with your check or money order for $89.95 to Airxcel, Inc., P.O. Box 4020, Wichita, KS 67204. A contract will be sent to you within a few weeks.
  • Page 10: Operation And Maintenance

    IX. OPERATION AND MAINTENANCE INSTRUCTIONS FOR 45000 SERIES ROOF TOP HEAT PUMPS AND CEILING PLENUMS i. GENERAL INFORMATION R410A Roof Top Heat Pumps NOTE: An optional auxiliary electric resistance High Pressure Switch Lockout Circuit heating assembly can be installed to take the chill...
  • Page 11: Operation

    115 volt electrical power. If the compressor on the on and off in this fashion until the selector switch is Heat Pump fails to start, check with your Airxcel, Inc. turned to another mode of operation. Service Center to determine that the proper wire size C.
  • Page 12: Wall Thermostat Identification And Operation

    Airxcel, Inc. support help may be accessed by e-mail at control box should be checked to determine whether RVPSupport@Airxcel.com. All written correspondence should be directed to: it is faulty.
  • Page 13 THIS PAGE INTENTIONALLY LEFT BLANK...
  • Page 14 RV Products Division INSTALLATION, D’UTILISATION ET D’ENTRETIEN POUR 45000 POMPES SÉRIE DE CHALEUR TABLE DES MATIERES VIII. Vérification fonctionnelle du système Informations générales Opération et maintenance Informations générales Sélection d’une pompe à chaleur appropriée III. Sélection de l’emplacement d’installation Panneau de Controle Installation de l’unité...
  • Page 15: Informations Générales

    à votre représentant deux devrait être installée à moins de 2,7 mètres (9 pi) Airxcel ou à Airxcel devraient contenir le nom et le du siège du conducteur. numéro de série du modèle du pompe a chaleur. Le...
  • Page 16 La série 45000 d’Airxcel exige un écart minimum de 2,54 cm 5. Fixation du pompe a chaleur au toit - L’ensemble de plafond comprend un cadre de montage. Fixez le pompe a chaleur au toit à...
  • Page 17: Oem Haut / Bas De Montage

    être utilisé pour permettre l’accès à l’élément chauffant par le dessous. En respectant les spécifications d’Airxcel, Inc. pour le câblage haute tension et l’ensemble des codes de l’électricité locaux Lorsque vous utilisez cette méthode d’installation de et nationaux, acheminez le câblage d’alimentation 115 V CC...
  • Page 18 REFER TO OEM DUCTING REQUIREMENTS FOR SUPPLY AND RETURN DUCTING INFORMATION. OEM DUCTING REQUIREMENT DOCUMENT IS AVAILABLE AT www.AIRXCEL.com. IT IS THE RESPONSIBILITY OF THE INSTALLER TO PROVIDE THE MEANS FOR SEGREGATION OF SUPPLY AND RETURN AIR. RETURN AIR SUPPLY AIR...
  • Page 19: Installation De L'accessoire De Chauffage Facultatif

    PAS ÊTRE INSTALLÉE EN UTILISANT LE HAUT / BAS CONFIGURATION DE MONTAGE. VIII. VÉRIFICATION FONCTIONNELLE DU Si vous installez un réchauffeur facultatif, positionnez le SYSTÈME réchauffeur dans l’ouverture de reprise d’air du pompe Airxcel, Inc. fabrique gamme étendue a chaleur, tel qu’illustré dans la Figure 7. Le support pompe a chaleurs de toit qui incorporent différentes...
  • Page 20: Vérification Fonctionnelle Du Système

    FIGURE 9 FIGURE 10...
  • Page 21 ROOFTOP UNIT MOUNTING FRAME ROOF STRUCTURE DUCT COLLAR CEILING ASSEMBLY CHUTE FABRIC DUCT MATERIAL CEILING FILTERS ASSEMBLY SHROUD CONTROL KNOBS FIGURE 11 GRILLES...
  • Page 22 GARANTIE dans la barre de recherche. RV Products Division AIRXCEL, INC. - RV Products Division • 3050 N. St. Francis St. • Wichita, KS 67219 316.832.3400 • www.AIRXCEL.com Coleman est une marque déposée de The Coleman Company, Inc., utilisée sous licence. Mach est une marque déposée.
  • Page 23 - CETTE PAGE EST INTENTIONNELLEMENT BLANK-...
  • Page 24: Opération Et Maintenance

    IX. MODE D’EMPLOI ET UTILISATION SÉRIES 45000 DES CLIMATISEURS DE TOIT DES PLÉNUM DE PLAFOND i. RENSEIGNEMENTS GÉNÉRAUX REMARQUE: Le montage de chauffage Elect-A-Heat Ces pompe a chaleurs de toit furent conçus pour optionnel est conçu pour enlever l’air froid à l’intérieur du fonctionner à...
  • Page 25: Functionnement

    Lorsque des centres de service autorisés Airxcel, Inc. Il est la température de l’air qui entre dans le pompe a recommandé...
  • Page 26: Identification Et Functionnement Du Thermostat Mural

    115 V. Au cas où le compresseur de pompe a chaleur refuserait de démarrer, contacter le centre d’entretien chaleur Coleman-Mach, veuillez communiquer avec votre Airxcel, Inc. pour déterminer si le pompe a chaleur détaillant. Vous pouvez également visiter notre site Web est alimenté par un câblage de calibre adéquate, si á...
  • Page 27 - CETTE PAGE EST INTENTIONNELLEMENT BLANK-...
  • Page 28: Optional Extended Warranty

    Apply today by filling out the application below and mailing it with your check or money order for $89.95 to Airxcel, Inc., P.O. Box 4020, Wichita, KS 67204. A contract will be sent to you within a few weeks. You should retain with your paperwork for proof of purchase.

This manual is also suitable for:

Coleman-mach 45000 series

Table of Contents