Fault messages
(cont.)
Displayed fault
System characteristics
code
103
Normal operation
104
Depending on configuration
of EM-EA1 extension (DIO
electronics module)
142
Burner in a fault state
160
Burner in a fault state
161
Burner in a fault state
163
Burner in a fault state
182
No DHW heating
183
No DHW heating
184
Burner in a fault state
185
Burner in a fault state
Cause
Internal communication
error, programming unit
External fault message in-
put active
Communication restriction
on CAN bus. INR
Communication error,
CAN bus
HBMU heat management
unit data memory access
fault
Checksum error, data
memory access, HBMU
heat management unit
Short circuit, outlet tem-
perature sensor (if instal-
led)
Lead break, outlet temper-
ature sensor (if installed)
Short circuit, flow temper-
ature sensor/high limit
safety cut-out
Lead break, flow tempera-
ture sensor/high limit safe-
ty cut-out
Troubleshooting
Measures
Check cables and plug-in connec-
tions between heat management
unit and HMI programming unit.
Check connected external device.
Check the fan unit for correct func-
tion. For this, check the stepper
motor of the fan unit (reference run
with mains ON).
If the fault persists, check the plug-
in connections and cables of the
CAN bus.
Check further CAN bus subscrib-
ers. If fault occurs repeatedly, re-
place fan unit.
Check connections to CAN bus
subscribers (INR, HBMU).
Check connections to external
CAN bus subscribers.
Reset the appliance.
If the fault occurs repeatedly, re-
place the HBMU heat management
unit. See chapter "Replacing the
HBMU heat management unit".
Reset the appliance.
If the fault occurs repeatedly, re-
place the HBMU heat management
unit. See chapter "Replacing the
HBMU heat management unit".
Check outlet temperature sensor
(plug X7, cores 3 and 4). Measure
sensor input on HBMU heat man-
agement unit. Set value: 3.3 V
with sensor disconnected
Check outlet temperature sensor
(plug X7, cores 3 and 4).
Check the flow temperature sen-
sor/high limit safety cut-out.
Check sensor lead. Replace faulty
component if necessary.
Reset the appliance.
Check the flow temperature sen-
sor/high limit safety cut-out. Re-
place faulty component if necessa-
ry.
Reset the appliance.