Page 1
PM-3133i Quick Start 1. Shipping Package This shipping package contains the following items 1 x PM-3133i module 1 x Quick Start Screw Driver x 1 Cable ties x 3 1.1. Caution & Warning The meter contains hazardous voltages, and should never be disassembled.
Page 2
Please read this operation manual carefully before using. Please re-confirm the measure position. Reconfirm the RST (ABC) phase sequence of the power system. Meter auxiliary power for PM-3133i series is DC +12V ~+48V. ICP DAS Co., LTD PM-3133i Quick Start V1.00...
Page 3
2.3. Current Input 1. The external CT’s are fragile, please handle with care. 2. The CT input of PM-3133i-xxxP series is in mV range. Only the ex-factory attached CT’s can be used. The other CT’s, for example, from panel will damage the instrument due to its large current (around 5A or mA).
Page 4
<Φ10 use 60A CT,Φ10~Φ16 use 100A CT,Φ16~Φ24 use 200A CT ,Φ24~Φ36 use 300A or 400A CT。 9. The maximum current value cannot exceed the CT rating. ICP DAS Co., LTD PM-3133i Quick Start V1.00 Page 4...
Page 5
Open the CT clip. there is a “K→L” mark. Make sure the power current Installation steps finished. direction follow the “K→L” mark on the CT and then close the CT clip. ICP DAS Co., LTD PM-3133i Quick Start V1.00 Page 5...