4

SPECIFICATIONS

Model name
Mode
Power supply (phase, cycle,voltage)
Input
Running current
External finish
Heat exchanger
Fan (drive) o No.
Fan motor output
Hi
Airflow
Fan
Lo
External static pressure
Operation control & Thermostat
Hi
Sound level
Lo
Drain connection
H
Dimensions
W
D
Weight
Model name
Mode
Power supply (phase, cycle,voltage)
Input
Running current
External finish
Heat exchanger
Fan (drive) o No.
Fan motor output
Fan
Airflow
External static pressure
Operation control & Thermostat
Sound level
Drain connection
H
Dimensions
W
D
Weight
PEA-RP200GAQ
Cooling
3PH 4W 50Hz 380-415V
kW
1.00
A
2.0
Galvanized steel
Cross fin coil
Centrifugal (direct) o2
0.77
65
CMM
1083
L/s
52
CMM
867
L/s
150
Pa
15
mmAq
Remote control & built in
51
dB(A)
48
dB(A)
R1
400
mm
1400
mm
634
mm
70
kg
lbs
154
PEA-RP400GAQ
Cooling
3PH 4W 50Hz 380-415V
kW
1.55
A
3.8
Galvanized steel
Cross fin coil
Centrifugal (direct) o2
1.3
120
CMM
2,000
L/s
150
Pa
mmAq
15
Remote control & built in
52
dB(A)
R1
595
mm
1947
mm
764
mm
130
kg
286
lbs
Heating
Cooling
3PH 4W 50Hz 380-415V
1.00
1.18
2.0
2.3
Remote control & built in
Heating
Cooling
3PH 4W 50Hz 380-415V
1.55
2.84
3.8
5.4
Centrifugal (direct) o2
Remote control & built in
10
PEA-RP250GAQ
Heating
1.18
2.3
Galvanized steel
Cross fin coil
Centrifugal (direct) o2
0.77
80
1333
64
1067
150
15
52
49
R1
400
1600
634
77
169
PEA-RP500GAQ
Heating
2.84
5.4
Galvanized steel
Cross fin coil
1.8
160
2,667
150
15
53
R1
595
1947
764
133
293

Hide quick links: