T&R KV30-40 Operating And Maintenance Manual

T&R KV30-40 Operating And Maintenance Manual

High voltage ac test set

Advertisement

Quick Links

OPERATING AND MAINTENANCE MANUAL
Product:
Type:
DESIGNED AND MANUFACTURED BY:
T & R Test Equipment Limited
Keens Lane, Worplesdon, Guildford, Surrey, GU3 3LS, United Kingdom
Telephone: 01483 235757
Fax.:
01483 235759
High Voltage AC Test Set
KV30-40
KV15-18
e-mail: sales@trtest.com
Web:
www.trtest.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KV30-40 and is the answer not in the manual?

Questions and answers

Summary of Contents for T&R KV30-40

  • Page 1 OPERATING AND MAINTENANCE MANUAL Product: High Voltage AC Test Set Type: KV30-40 KV15-18 DESIGNED AND MANUFACTURED BY: T & R Test Equipment Limited Keens Lane, Worplesdon, Guildford, Surrey, GU3 3LS, United Kingdom Telephone: 01483 235757 e-mail: sales@trtest.com Fax.: 01483 235759 Web: www.trtest.com...
  • Page 3 GENERAL SAFETY STATEMENT The following safety precautions should be reviewed to avoid injury to the user and damage to the product (and other products connected to it). To avoid potential hazards only use this product as specified. Only suitably qualified personnel should use this equipment. Servicing of this product should only be carried out by suitably qualified service personnel.
  • Page 5: Table Of Contents

    CONTENTS Description of Equipment Operating Procedures Maintenance Instructions Standard Accessories Overall Performance Specification Calibration Results Test Certificate Revision...
  • Page 7: Description Of Equipment

    DESCRIPTION OF EQUIPMENT Electrical Specification Output Voltage Control Overload Protection Metering Construction...
  • Page 8: Electrical Specification

    The minimum supply requirements are 1200VA: 1.1.3 The output voltage, current and duty cycle are as follows: Output Voltage Output Current 1 Output Current 2 KV30-40 30kV 20mA 40mA KV15-80 15kV 40mA 80mA Output current 1 is the continuous current rating.
  • Page 9: Output Voltage Control

    Output Voltage Control 1.2.1 The output is controlled from zero by means of a regulating transformer. The transformer is operated by means of a control knob which is located on the front panel of the control unit. To increase the output voltage the knob is turned in a clockwise direction.
  • Page 10: Overload Protection

    Overload Protection 1.3.1 The equipment is fitted with fixed and variable overload protection circuits as standard. 1.3.2 Fixed overload The fixed overload protection system senses any rapid increase in the load current which exceeds approximately 120% of the full load current in the high voltage circuit. The circuit will respond more quickly to low impedance faults.
  • Page 11: Metering

    Metering 1.4.1 The equipment is provided with the following metering: A moving coil dual range kilovoltmeter monitoring the output voltage from the equipment. A moving coil single range milliammeter monitoring the secondary current of the high voltage transformer.
  • Page 12: Construction

    Construction 1.5.1 The equipment is housed in a robust case with recessed carrying handles. All the controls and metering are located on the front panel together with all external connections.
  • Page 13 OPERATION Connections Front Panel Functions Method of Operation...
  • Page 14 Connections (See Figure 1) 2.1.1 The input lead on the control unit should be connected to a suitable three pin plug. 2.1.2 Connect the earth lead from a reliable efficient earth to the earth terminal on the equipment. 2.1.3 Connect the earth hook lead to the earth terminal on the test set and place the hook on the test object's high voltage terminal.
  • Page 15 Figure 1 Connection showing earthed test object – before start of test screened part of HV cable supply cable earth screen limit and stress relief HV test set unscreened part of HV cable earth return test object earth stick IMPORTANT: There must be 20cm minimum clearance between the unscreened section of HV output cable and earth.
  • Page 16 Front Panel Control Functions 2.2.1 ITEM FUNCTION Power ON/OFF switch To isolate equipment from the mains supply. Key operated Power ON lamp To indicate that the supply is connected to the equipment, power switch is closed and the supply fuse is intact. H V OFF illuminated Indicates HV output is OFF when lit.
  • Page 17 Front Panel Layout EARTH RATING MAINS FUSE IN VOLTAGE SELECTOR DANGER HIGH VOLTAGE TRIP X 0.5 MILLIAMPS RESET ÷10 KV RANGE HV OUTPUT 100% POWER OUTPUT CONTROL TYPE KV30-40 T&R TEST EQUIPMENT...
  • Page 18 Method of Operation 2.3. 1 Connect the equipment as described in Section 2.1. 2.3. 2 Remove the power switch operating key before connecting the equipment to the main supply. This will ensure the equipment is in the OFF position as the key is only removable in that position.
  • Page 19 MAINTENANCE The switches and contactors should be occasionally examined for signs of wear and contact erosion. Badly eroded contacts should be replaced immediately. The voltage regulator should be regularly examined, particularly in respect of the brushes, in order that the latter may be replaced before excessive wear has taken place. The intervals between inspection and renewal of the brushes will depend upon the amount of usage.
  • Page 20: Standard Accessories

    STANDARD ACCESSORIES Spare fuses supplied 1 off T5A 1¼ inch 1 off F10A 1¼ inch The following items are provided with the equipment: Mains input lead. 2 keys (for mains switch). ON/OFF 5 metre earth lead fitted with clip and tag. Type ES30-40 earthing stick.
  • Page 21: Overall Performance Specification

    OVERALL PERFORMANCE SPECIFICATION Insulation resistance at 1000V DC Not less than 10 megohms between mains input and frame. Applied voltage test 2kV RMS for 1 minute between mains input and frame Accuracy of instruments KV meter ±1.5% at full scale mA meter ±1.5% at full scale H V Transformer 2.5kV RMS for 1 minute between primary and earth...
  • Page 23: Calibration Results

    Equipment's Standard Range KV meter KV meter mA meter mA meter High Range (x1) 10.0 15.0 Low Range (x0.5) 5.00 Unit Type KV30-40 Equipment's Standard Equipment's Standard Range KV meter KV meter mA meter mA meter 10.0 High Range (x1) 15.0...
  • Page 25: Test Certificate

    PRODUCT SERIAL NUMBER: TEST PROCEDURE: As routine test sheet:- KV15-80 rts.doc TESTED BY: ........PASSED BY: ........DATE: ..........PRODUCT TYPE: KV30-40 PRODUCT SERIAL NUMBER: TEST PROCEDURE: As routine test sheet:- KV30-40 rts.doc TESTED BY: ........PASSED BY: ........DATE: ..........
  • Page 27: Revision

    REVISION Product/Type: High Voltage AC Test Set/KV30-40 & KV15-18 File: KV30-40 and KV15-80 manual v10.doc [DJ1] Author: D. Buckle Issue/Date: 10 / 12.06.2001 Modified By: D. Buckle Checked By: I.D.W. Lake Date: 12.06.2001...
  • Page 28 Drawings Required A2/000308 latest issue A2/000542 latest issue...