Download Print this page
Xylem IQ SensorNet Quick Start Manual

Xylem IQ SensorNet Quick Start Manual

Miq/ic2 module

Advertisement

Quick Links

IQ SensorNet MIQ/IC2 Module
QUICK START GUIDE
Overview
The MIQ/IC2 current input module provides two 0/4 - 20 mA current
inputs for IQ SensorNet and thus enables to connect external sensors
via their current output. Measured values of the external sensors can
be displayed, recorded and processed like the measured values from
IQ SensorNet.
Examples:
Connecting flow meters to IQ SensorNet
Connecting level meters to IQ SensorNet
Connecting analyzers to IQ SensorNet
Connecting pressure sensors to IQ SensorNet
Scope of Delivery:
MIQ/IC2 module
4 x cable glands (clamping range 4.5-10 mm) with seals and blind
plugs
4 x ISO blind nuts M4 with suitable cheese-head screws and plain
washers
2 x countersunk screws M3x6 to close the module lid (+ 2
replacement screws)
1 x contact base with fixing screws
Materials Required
To set up the MIQ/IC2 module you will need the following tools:
Cable stripping knife
Wire stripper
Phillips screw driver
Small screw driver
Cable
Quick Start Guide
YSI Municipal Water
Figure 1: MIQ IC2 Module
TABLE OF CONTENTS:
1. Setup
2. Wiring
3. Configuration
XA00166

Advertisement

loading

Summary of Contents for Xylem IQ SensorNet

  • Page 1 Overview The MIQ/IC2 current input module provides two 0/4 - 20 mA current inputs for IQ SensorNet and thus enables to connect external sensors via their current output. Measured values of the external sensors can be displayed, recorded and processed like the measured values from IQ SensorNet.
  • Page 2 Warning This document is not intended to replace the MIQ/IC2 module operation manual. Please use the operating manual as a reference during the following functions; installation, operation, cleaning, maintenance and troubleshooting. Step By Step Instructions Install all cable glands to the bottom of the MIQ/IC2 module as shown below Connect the cable to the terminal strip Open the MIQ/IC2 module.
  • Page 3 Loop Powered Devices: The 24V power supply in the MIQ/IC2 is rated for 240mA. If powering two devices make sure the current draw of the entire 24V loop (the devices and isolators) Figure 1: Press the “S” button on the IQ SensorNet controller doesn’t exceed 240mA.
  • Page 4 Scroll down to the “Setting of sensors and Select the “Measuring range” column and diff. sensors” option and press “OK”. press “OK”. Press “Continue” Customize the following settings to the appropriate values...
  • Page 5 Measuring range Decimal places Display value (0/4mA) Display value (20 mA)
  • Page 6 Display unit Measured parameter Error detection Error threshold...
  • Page 7 If only one device is connected to MIQ/IC2 module = Inactive If two devices are connected to MIQ/IC2 module = Active YSI, a Xylem brand +1.937.767.7241 1725 Brannum Lane info@ysi.com Yellow Springs, OH 45387 YSI.com/IQSN YSI.com/IQSN © 2021 Xylem, Inc. XA00166 0621...