SETTING AND USING METHOD
28
• When setting CT type
* W H M
W / P U L S E
1 .
N O T
U S E
2 .
1 W / P U L S E
3 .
2 W / P U L S E
* W H M
W / P U L S E S E L E C T *
7 .
1 0 W / P U L S E
8 .
1 0 0 W / P U L S E
9 .
C T / P T
C T & P U L S E
R A T I O
C T : 0 0 0 0 0
,
W H M 1
[ P u l s e / k W h ]
C O N S U M E
U N I T
1 .
O U T D O O R
2 .
I N D O O R
U N I T
I N D O O R
A D D R E S S
( S T A R T ) → ( E N D )
( 0 0 ) → ( 0 0 )
W H M 1 : C T / P T , I D U , 0 0 - 0 0
W H M 2 : N O T
U S E
W H M 3 : N O T
U S E
W H M 4 : N O T
U S E
After setting all wattmeters, press the MENU button to save the setting and move to the initial
screen.
S E L E C T *
D O W N
U P
S E T
P r : 0 0 0 0 0
S E L E C T
U N I T
S E T
Press the (▼) button to set CT/PT from the power
consumption setting screen per pulse.
When 9. CT/PT item flashes, press the SELECT
button to enter CT, Pr input window.
It proceeds in the order of Set CT, device
constant ' Set power consumption device ' Set
connected indoor address.
- CT: As the device to reduce the current so that
the measuring device can take the measurement,
enter the rate indicated on the product to the CT
item.
Ex) when using 100:1 CT, enter 100 to the CT
item.
- Pr: As the device constant value, it is displayed
as ratio of output pulse per power consumption
of wattmeter.
For the device constant value, enter the value dis-
played on wattmeter [Pulse/kWh]
Ex) when using 2500 [Pulse/kWh] wattmeter,
enter 2500 to Pr item.
After setting the applicable item, press the
SELECT button to save the setting and to move to
the next stage.
Setting information is reflected to the detail setting
window.