Maintenance (continued)
2) Lossnay cores
Use a vacuum cleaner to suck up the dust and dirt on the exposed
surfaces of the Lossnay cores.
Use a soft brush only to clean exposed surface areas.
Do NOT wash in water.
Vacuum cleaner
(with brush attachment)
CAUTION
l Do not use the hard nozzle of the vacuum cleaner. It may
damage the exposed surfaces of the Lossnay cores.
l Under no circumstances should the Lossnay cores be washed
in water.

Specifications

Running current
Model name
(A)
LGH-15RVX-ER
0.40
LGH-25RVX-ER
0.48
LGH-35RVX-ER
0.98
LGH-50RVX-ER
1.15
LGH-65RVX-ER
1.65
LGH-80RVX-ER
1.82
LGH-100RVX-ER
2.50
LGH-150RVX-ER
3.71
LGH-200RVX-ER
4.88
* The above values apply during Lossnay ventilation when the fan speed is set to Fan speed 4 at the rating pressure loss and 230 V / 50 Hz.
* For the specifications at the other frequency or voltages, contact your dealer.
* The values given in the table for the noise level reflect the levels measured at a position 1.5 meters immediately below the unit in an anechoic chamber.
* Noise change or increase may occur because of the Bypass-Automatic function or Automatic fan speed change by timer setting and/or other
functions.
* Temperature Exchange efficiency (%) are based on winter condition.
* Mitsubishi Electric measures products according to Japan Industrial Standard (JIS B 8628), therefore Q-H curves are measured by chamber method.
* On-site commissioning measurements by pitot tube method could be as much 20% difference from JIS test room conditions. If the measuring
point is close to sources of turbulence like bends, contractions and dampers etc, it is difficult to measure air volume correctly. A straight duct
length more than 10D (D=duct diameter) from the source of turbulence is recommended for correct measurement. On-site measurement
should therefore be measured in accordance with BSRIA guideline (Commissioning Air System. Application procedures for buildings
AG3/89.3(2001))

After-sales servicing

Consult with your dealer about the after-sales services provided for
this Lossnay product.
Inspect your unit of good service!
Attentive inspection
Have you
noticed?
Lossnay core
Air volume
Input power
(W)
(m
/h) (L/S)
3
49
150
42
62
250
69
140
350
97
165
500
139
252
650
181
335
800
222
420
1000
278
670
1500
417
850
2000
556
● Fan do not run when the unit is turned on.
● Abnormal noises or vibrations while the unit is running.
● Retarded or irregular rotations.
(Motors are component which requires maintenance.)
● Burnt odor.
● Corroded or damaged installation section.
Assembly after maintenance
Bearing in mind the following points, assemble the parts following
the sequence for their removal in reverse.
l Arrange the Lossnay core with the air filter side downward.
l The filter for LGH-15 and 35RVX-E has front and back side. Set
the "FRONT" (printed) side of the filter on the outer side.
Note
l If
are indicated or the remote controller, turn off the
indication, after maintenance.
Static pressure
Exchange efficiency (%)
(Pa)
Temperature
Heating
95
80
85
79
160
80
120
78
120
77
150
79
170
80
175
80
150
80
If you hear strange sounds, if no air is blown out or if some other
trouble occurs, switch off the power and contact your dealer. Consult
with your dealer concerning the cost of inspection or repair work.
Eng-4
Noise (dB)
Enthalpy
Below the unit
Cooling
73
71
28
69.5
68
27
71.5
71
32
69
66.5
34
68.5
66
34.5
71
70
34.5
72.5
71
37
72
70.5
39
72.5
71
40
Turn off the unit. Then,
contact your dealer for
Stop
prevention of failure or
running.
hazard. The dealer should
appraise the possible cost.
Weight
(kg)
20
23
30
33
38
48
54
98
110