7.2.5 USER MENU E: DELAYED START-UP
When starting up the NRG-Temp in Comfort program
after a power interruption, it can be interesting to
start different heating circuits separately. You can set
a delay on the start-up of each thermostat by using
the delayed start-up function.
Possible values: OFF / 1, 2... 15 minutes
Factory set value: OFF
7.2.6 USER MENU F: FROST PROTECTION FOR OFF
PROGRAM
When the thermostat is in the Standby program, the
floor can be protected against frost using the Frost
Protection menu.
Fixed set point: 7°C
Possible values: ON / OFF
Factory set value: OFF
7.2.7 USER MENU G: PROPORTIONAL
REGULATION
In room sensing mode, the proportional regulation
re d u ce s t h e te m p e ra t u re va r i a t i o n s w h e n
approaching the required temperature.
Possible values: ON / OFF
Factory set value: ON
7.2.8 USER MENU H: SET BACK TEMPERATURE
OFFSET
With the external set back signal (pilot wire feature),
the comfort temperature is reduced by a number of
degrees.
This Setback Temperature OFFSET is neglected
when the external set back signal is not present or
the pilot wire is not connected.
Possible values: -1.0 to -7.0°C
Factory set value: -3.5°C
27