Panduit VeriSafe AVT Instruction Manual

Panduit VeriSafe AVT Instruction Manual

Absence of voltage tester

Advertisement

Quick Links

For use in Hazardous Locations Class I, Division 2 or equivalent Class I, Zone 2
© Panduit Corp. 2018
The VeriSafe Absence of Voltage Tester is a permanently-mounted tester that is used to verify a circuit is de-
energized prior to opening an electrical enclosure. Once installed, a push of a button enables qualified electrical
workers to verify the absence of voltage and see an active indication when the absence of voltage is confirmed.
The Indicator Module is designed for a 30-mm notched panel knockout and the Isolation Module can be mounted
to DIN rail or surface mounted using screws.
TO REDUCE THE RISK OF INJURY, USER
MUST READ INSTRUCTION MANUAL
Email:
techsupport@panduit.com
EU Website:
www.panduit.com/emea
EU Email:
emeatoolservicecenter
@panduit.com
VeriSafe AVT
Absence of Voltage Tester
Instruction Manual
Models: VS-AVT2-C02L03, VS-AVT2-C08L10
NOTE: In the interest of higher quality and value, Panduit products are
continually being improved and updated. Consequently, pictures may vary from
the enclosed product.
NOTE: Updates to this Instruction Manual may be available. Check
www.panduit.com for the latest version of this manual.
www.panduit.com
Technical Support:
Tel: 1-866-405-6654
Panduit Europe • EMEA Service Center
Almelo, Netherlands
Tel: +31-546-580-452 • Fax: +31-546-580-441
B21075
Rev: 00 04-2018
Original Instructions

Advertisement

Table of Contents
loading

Summary of Contents for Panduit VeriSafe AVT

  • Page 1 DIN rail or surface mounted using screws. TO REDUCE THE RISK OF INJURY, USER MUST READ INSTRUCTION MANUAL NOTE: In the interest of higher quality and value, Panduit products are continually being improved and updated. Consequently, pictures may vary from the enclosed product.
  • Page 2: Table Of Contents

    INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 Table of Contents Safety Information ..........................2 Information de Sécurité ........................3 Components ............................ 4 Output Contacts ..........................4 Technical Specifications ........................5 Dimensions ............................7 Schematics ............................8 Installation Considerations ......................11 Installation Instructions........................13...
  • Page 3: Safety Information

    Should a problem occur during installation, operation or maintenance of the VeriSafe AVT, contact Panduit using one of the technical support or customer service numbers listed on the cover of this manual. Contact Panduit if you have any product problems related to the safety function of the product.
  • Page 4: Information De Sécurité

    • En cas de problème lors de l'installation, du fonctionnement ou de la maintenance de VeriSafe AVT, contactez Panduit en utilisant l'un des supports techniques ou les numéros de service clientèle figurant sur le couvercle de ce manuel. Veuillez contacter Panduit si vous avez des problèmes de produits liés à...
  • Page 5: Components

    © Panduit Corp. 2018 Components VeriSafe Indicator Module Faceplate Color Note: The images shown in this manual are of the VeriSafe AVT model VS-AVT-C08-L10 The components of the Panduit VeriSafe Absence of Voltage Tester (AVT) Output Contacts The AVT includes a set of redundant dry contact signal outputs for optional use with control systems. These contacts are located on the Isolation Module.
  • Page 6: Technical Specifications

    Industrial, Scientific and Medical (ISM) radio frequency generators. Conformity Marking for European Economic Area Restriction of hazardous substances RoHS NOTE: By design and installation guidelines the VeriSafe AVT is not impacted by the occurrence of phenomena from IEC 61000-4-16 B21075_00 Page: 5 of 20 04-2018...
  • Page 7 INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 Applications Area Classification - UL - Industrial Control Equipment for Groups A, B, C, D Class I, Division 2 Temperature Classification - T3 Hazardous Locations Area Classification - Suitable Equivalency Group IIA, IIB, IIC...
  • Page 8: Dimensions

    INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 Dimensions Isolation Module MOUNTING HOLES (3) Units = inches [mm] Indicator Module Units = inches [mm] Panel Knockout The Indicator Module is designed for use with a standard 30 mm knockout with notch.
  • Page 9: Schematics

    INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 Schematics Warning: The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indication of absence • of voltage. Sensor leads must not be mechanically connected with each other for the device to verify connection to the circuit.
  • Page 10 INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 Single-Phase: 2 Wire + PE Single-Phase: 2 Wire + PE, Redundant Detection Lead Single-Phase: 3 Wire + PE Corner Grounded DELTA: 3 Wire + PE High-Leg DELTA: 3 Wire + Neutral + PE...
  • Page 11 INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 DC System: 2 Wire + PE, Redundant Detection Lead B21075_00 Page: 10 of 20 04-2018...
  • Page 12: Installation Considerations

    AVT if the fuse is open. The circuits in the VeriSafe AVT Isolation Module that are intended to be in contact with the branch circuit are designed to provide isolation overvoltage up to 6kV.
  • Page 13 Connectivity Test Each time the absence of voltage test is initiated, the VeriSafe AVT performs a series of diagnostics and checks in addition to testing for absence of voltage. One step in this sequence involves a “connectivity test.” The purpose of the connectivity test is to ensure that each detection lead is in contact with a conductor.
  • Page 14: Installation Instructions

    INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 Installation Instructions Warning: The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indication of absence • of voltage. Sensor leads must not be mechanically connected with each other for the device to verify connection to the circuit.
  • Page 15 INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 Insert the other end of the AVT 7. Terminate the sensor and ground leads. Route Sensor Leads and AVT System System Cable in the connector Secure the sensor leads to the conductors and...
  • Page 16: Commissioning Checklist

    INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 Commissioning Checklist: □ Visually inspect the AVT: o AVT system cable: Verify cable is locked into place on both the Indicator Module and Isolation Module. o Indicator module: Ensure o-ring is in place. Check that retaining nut is secure. Verify battery is installed and battery cap is locked into place.
  • Page 17: Operating Instructions

    INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 Operating Instructions Warning: • To avoid electric shock, always de-energize power before entering an electrical enclosure. • Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.
  • Page 18: Troubleshooting

    Should a problem occur during installation, operation or maintenance of the VeriSafe AVT, contact Panduit using one of the technical support or customer service numbers listed on the cover of this manual. Contact Panduit if you have any product problems related to the safety function of the product. The product model number and serial number are printed on the Isolation Module and Indicator Module labels.
  • Page 19: Maintenance

    TL-5903 AA, ER14505 3.6 Volt Lithium Battery Xeno Energy XLP-060F Saft LS14500 Table 1: Approved VeriSafe AVT batteries Grip the Indicator Module Twist the Indicator Module cap Remove the cap. Grip the battery tray and Cap. counterclockwise approximately 90 slide it out until you feel a degrees, until you feel a stop.
  • Page 20: Avt System Cable Removal

    INSTRUCTION MANUAL VeriSafe AVT © Panduit Corp. 2018 AVT System Cable Removal 1. Grip the Retention Spring on both Continue holding the Retention Spring down sides. while pulling back on the right-angle connector to release the AVT System Cable. 2. Pull down on the Retention Spring approximately 1/16 inch [1.5 mm].
  • Page 21: Warranty

    Panduit product, and each part or component of the Panduit product, will comply with Panduit’s published specifications and will be free from defects in material and workmanship for a period of 1 year from the date of invoice from Panduit or its authorized distributor, not to exceed 18 months from the original date of shipment from Panduit’s facility.