Alarms

Frame heating (Inventus F)
ENGLISH
HA High temperature alarm
The temperature inside the cabinet has exceeded the set alarm temperature. The alarm
can be instigated by sudden icing of the evaporator. Initiate additional manual defrost.
See instructions on the previous page. Ensure the cabinet has not been loaded with warm
products. Check that a door has not been left open. Check that any product is not blocking air
circulation within the cabinet. The cabinet is meant to keep ready chilled products cold.
LA Low temperature alarm
The temperature inside the cabinet has fallen below the set value. Ensure that the products
put into the cabinet are not too cold.
The temperature alarm will reset automatically after the interior of the cabinet returns to the
set temperature range. If this does not happen, move the products to another cabinet and
contact your service provider.
dA Door open alarm
Close the door carefully and the alarm will reset automatically.
HA2 Condenser alarm
The condenser/filter needs to be cleaned. Switch cabinet off and remove the plug from the
wall socket. Clean the condenser /filter (see chapter "Cleaning").
Check also that air circulation to the condenser is not blocked or that the ambient temperature
is not too high. If the alarm still does not stop, remove products to another cabinet and
contact your service provider.
P1 Thermostat probe failure *
P2 Evaporator probe failure *
P3 Condenser probe failure *
*The cabinet operates on its standby system and will hold normal temperature. Reset the
alarm signal and immediately contact your service provider.
EE Data failure
To reset an 'EE' Alarm on the display and resume normal function of the equipment press any
button for 3 seconds. After this 'rSt' message will be displayed again for 3 seconds and the
equipment should return to normal function.
Freezer cabinets are supplied with a doorframe heater,
this is 'on' when the cabinets is shipped from our
factory. The vast majority of time this heater is not
required and it can be switched 'off' to reduce energy
consumption. When there is extremely high humidity
you may notice condensation on the doorframe in this
case switch the heater 'on' using the switch behind the
top cover.
Note!
Our energy consumption tests are made with the doorframe heater 'off' .