5.6
Positioning the probe - electrode
Before securing the burner to the boiler, check
(through the opening of the blast tube) that the
probe and electrode are correctly positioned, as in
Fig. 13.
ATTENTION
If the probe or electrode is not correctly positioned, you must:
remove the screw 1)(Fig. 12);
take out the inner part 2)(Fig. 12) of the head and then
calibrate them.
Do not rotate the probe but leave it as in Fig. 13; if
it is too close to the ignition electrode, it could
damage the control box amplifier.
ATTENTION
Respect the dimensions shown in Fig. 13.
ATTENTION
Installation
PROBE
D1209
D1210
ELECTRODE
17
GB
Fig. 12
Fig. 13
20168422