GE Zoneline 4000 Series Use And Care Manual page 4

Advertisement

Auxiliary Controk
Additional controls are located
behind the room cabinet.
To remove the room cabinet,
see page 5.
VENT
OPEN
knob
This
CLOSE at the
factory. When it is in this position,
the vent door is closed and only
indoor air is filtered, cooled or
heated and circulated by the air
conditioner.
Switching the knob to OPEN opens
the vent door to allow some outside
air to enter the room. However,
cooling or heating effectiveness is
reduced when the control is set at
OPEN, so we suggest you don't
keep it there long.
If the knob is not set all the way in
CLOSE position, the vent light will
remain on.
TEMP
OVERRIDE
SETBACK (~ ;;;;::EL
FAN
CYCLE (~) CONT
HEATING ECONOMY—
NORMAL ~~) MAXIMUM ~
TL2 TL1
'EAT U'MAL
TL2 TL1
Unit Wwe; Swikh
This switch is set at
ON at the
factory to allow the air conditioner
to operate in the cool, heat or fan
only modes and the Freeze Sentinel,
Heating Economy Switch and Temp
Override to operate if it is needed.
If this switch is set at OFF, the air
conditioner will not operate in any
mode and the Freeze Sentinel,
Heating Uonomy Switch and
Temp Override will not function.
Caution: The Unit Power Switch
is not a power disconnect. If all
power must be disconnected from
the unit, remove the line cord plug
from the wall outlet, or remove the
fuses, or turn off the circuit
breakers at the power panel.
4
'Fan Cycle Switih
This switch is set at CONT at the
factory to provide continuous fan
operation in cool or heat modes. If
you want the fan to cycle on and off
with the compressor or resistance
heater, set the switch at ~CLE.
\
Heating Wonomy
For maximum heating economy,
this switch is set at MAXIMUM
at the factory. Until the outside air
temperature drops to 15°F., the heat
pump is the primary source of heat.
\
At 15°F. and below, full resistance
heat takes over.
Set this switch at NORMAL and
the change from heat pump to
resistance heating occurs when
the outside air temperature drops
to 35°F.
Temp Limit Switih
The TEMP LIMIT switch is used
to adjust the thermostat range. Set
it to limit the lowest temperature
that can be obtained on cooling and
the highest temperature that can k
obtained on heating.
COOL and HEAT settings range
from NORMAL to TL3. Both
controls are set at NORMAL at
the factory.
Normal
57-
TL1
71-
TL2
77-
TL3
83- 91°
Heating
90°
57- 90°
90°
57- 77°
57- 73°
90°
57- 68°