❶Power supply:
3N  400V/50Hz:
EASY PRO E-100 (min. 5x2,5mm
Protection B10)
EASY PRO E-150 (min. 5x2,5mm
Protection B16)
EASY PRO E-200 (min. 5x4,0mm
Protection B20)
In the event of a hazard arising from the unintentional reset of the thermal
switch, this equipment should not be powered by an external connecting device,
such as a time switch, or a disconnector connected to the circuit, which is
regularly switched OFF and ON during use.
15 CONTROLS – OPTIONAL ELEMENTS
PIC. 15.1 3-step regulator with built in
thermostat.
S-TOUCH + S-ECM
PIC. 15.2 Touch screen controller + control
system.
19/52 User Instructions
2
;
2
;
2
;
S-C
❷Power supply:
1N  230V/50Hz:
EASY PRO E-100 (min. 3x1,5mm
Protection B10)
EASY PRO E-150 (min. 3x1,5mm
Protection B16)
EASY PRO E-200 (min. 3x2,5mm
Protection B20)
FAN AUTO - fan operation depends on
the temperature.
FAN CONT - continuous fan operation
HEAT - heating function
FAN - deactivate the thermostat for FAN
CONT
COOL - reversal of the operation logic of
the thermostat
S-Touch:
Temperature setting range: +5 ... + 35
Operating temperature range: -10 ... +
o
60
C Protection degree: IP30
Supply voltage: 24 VDC
S-ECM:
Operating temperature range: -10 ... +
o
60
C Protection degree: IP54
Supply voltage: 230 V / 50 Hz