Toshiba MMD-AP0186HP1-E Service Manual page 91

Table of Contents

Advertisement

CODE No. list (Example)
CODE No. (DN)
01
Filter sign lighting time
02
Filter pollution leve
03
Central control address
06
Heating suction temperature shift
0d
Existence of automatic COOL/HEAT mode
0F
Cooling only
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
Temperature range of cooling / heating
1E
automatic SW control point
28
Power failure automatic recovery
31
Vent Fan (Single operation)
32
Sensor SW (Selection of static pressure)
5d
High ceiling select
60
Timer setting (wired remote controller)
F0
Swing mode
D0
Power save operation
Type
Code No. [10]
Setting data
0006
Concealed Duct High Static Pressure Type
Item
Type
Model abb. name
MMD-AP
Setting data
Depending on Type
0000: standard
0099: Not determined
0002: +2 ‹C (Floor standing type: 0)
0001: No auto mode cooling / heating
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
0003: 3 deg (Ts } 1.5)
0000: None
0000: Not possible
0000: Body sensor
0000: Standard
0000: Available
0001: Standard
0001: Standard
Indoor unit capacity
CODE No. [11]
Setting data
∗∗∗
HP
0000*
0001
0002
0003
0004
0005
0006
0007
0008
0009
0010
0011
0012
0013
0014
0015
– 91 –
Factory-set value
* Automatically selection
by connected outdoor
unit
Model
Setting data
Invalid
0016
007 type
0017
0018
009 type
0019
0020
012 type
0021
0022
015 type
0023
0024
018 type
0025
0026
024 type
0027
027 type
0028
030 type
~
0034
036 type
Model
048 type
056 type
072 ype
096 type

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents