Direct expansion fan coil unit

Advertisement

PF4MNA
DIRECT EXPANSION
FAN COIL UNIT
NOTE: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory- -authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local
building codes and the current editions of the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.
Recognize safety information. This is the safety- -alert symbol
When you see this symbol on the unit and in instruction manuals,
be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety- -alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
Installation Instructions
PAGE
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . .
. . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
FOR R410A REFRIGERANT
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
!
1
1
ELECTRICAL SHOCK HAZARD
1
Failure to follow this warning could result in personal injury
1
or death.
1
Before installing or servicing unit, always turn off all power
to unit. There may be more than 1 disconnect switch. Turn
2
off accessory heater power, if applicable.
4
4
7
7
Model PF4MNA Fan Coils are designed for flexibility and can be
used for upflow, horizontal, or downflow (kit required) and
7
manufactured and mobile home applications. These units are
8
designed to meet the low air leak requirements currently in effect.
9
Because of this, the units need special attention in the condensate
pan and drain connection area and when brazing tubing. These
9
units are designed specifically for R- -410A refrigerant and must be
9
used only with R- -410A refrigerant air conditioners and heat
10
pumps as shipped. These units are available for systems of 18,000
through
60,000
12
Factory- -authorized, field- -installed electric heater packages are
available in sizes 5 through 30kW. See Product Data literature for
available accessory kits.

HEATER PACKAGES

Factory- -approved, field- -installed, UL listed heater packages are
available from your equipment supplier. See unit rating plate for a
list of factory- -approved heaters. Heaters that are not factory
approved could cause damage which would not be covered under
the equipment warranty.
Step 1 - Check Equipment
Unpack unit and move to final location. Remove carton taking care
not to damage unit. Inspect equipment for damage prior to
installation. File claim with shipping company if shipment is
damaged or incomplete.
Locate unit rating plate which contains proper installation
information. Check rating plate to be sure unit matches job
.
specifications.
SIZES 018 TO 061
WARNING

INTRODUCTION

Btuh
nominal
cooling
INSTALLATION
capacity.

Advertisement

Table of Contents
loading

Summary of Contents for Payne PF4MNA

  • Page 1: Table Of Contents

    Step 6 - - Refrigerant Flow- -Control Device ....Model PF4MNA Fan Coils are designed for flexibility and can be used for upflow, horizontal, or downflow (kit required) and Step 7 - - Condensate Drains .
  • Page 2: Step 2 - Mount Unit

    Step 2 — Mount Unit NOTE: Gasket kit number KFAHD0101SLP is also required for all downflow applications to maintain low air leak/low sweat Unit can stand or lie on floor, or hang from ceiling or wall. Allow performance. space for wiring, piping, and servicing unit. C.
  • Page 3 NOTE: Modular units can be disassembled and components Horizontal Right Conversion of Units With A- -Coils moved separately to installation area for reassembly. This process 1. Remove blower and coil access panels. (See Fig. 6.) accommodates small scuttle holes and limiting entrances to installation sites.
  • Page 4: Step 3 - Air Ducts

    11. Remove insulation knockouts on right side of coil access Ductwork Acoustical Treatment panel. Metal duct systems that do not have a 90_ elbow and 10- -ft (3m) of 12. Remove 2 oval coil access panel plugs and reinstall into main duct to first branch takeoff may require internal acoustical holes on left side of coil access panel and fitting panel.
  • Page 5 Before proceeding with electrical connections, make certain that FAN COIL THERMOSTAT (CONTROL) supply voltage, frequency, phase, and ampacity are as specified on the unit rating plate. See unit wiring label for proper field high- - and low- -voltage wiring. Make all electrical connections in accordance with the NEC and any local codes or ordinances that may apply.
  • Page 6 FAN COIL SECONDARY HEAT PUMP THERMOSTAT (CONTROL) (CONTROL) ODTS PRIMARY A05182 Fig. 16 - - Transformer Connections A94061 Fig. 13 - - Wiring Layout Heat Pump Unit (Cooling and Heater Staging 2- -Stage Heat with 1 Outdoor Thermostat) CAUTION FAN COIL HEAT PUMP THERMOSTAT (CONTROL)
  • Page 7: Step 5 - Refrigerant Tubing Connection And Evacuation

    Step 6 — Refrigerant Flow- -Control Device 061 models is done at the motor. (See Fig. 18.) To change motor The PF4MNA fan coil is equipped with R- -410A refrigerant TXV. speeds, disconnect fan lead from terminal 2 and move to desired Use outdoor units designed for R- -410A refrigerant only.
  • Page 8: Step 8 - Accessories

    CAUTION CAUTION UNIT OR PROPERTY DAMAGE HAZARD PROPERTY DAMAGE HAZARD Failure to follow this caution may result in product or Failure to follow this caution may result in product or property property damage. damage. The conversion of the fan coil to downflow requires special Shallow running traps are inadequate and DO NOT allow proper procedures for the condensate drains on both A- -coil and condensate drainage.
  • Page 9: Step 9 - Sequence Of Operation

    CARE AND MAINTENANCE CONTROL BOARD To continue high performance and minimize possible equipment FAN RELAY G T C C C failure, it is essential that periodic maintenance be performed on 230VAC this equipment. Consult your local dealer as to the proper frequency of maintenance contract.
  • Page 10: Airflow Performance Tables

    AIRFLOW PERFORMANCE TABLES Table 1 – Airflow Performance (CFM) TOTAL EXTERNAL STATIC PRESSURE (in. wc) MODEL BLOWER SPEED 0.10 0.20 0.30 0.40 0.50 0.60 High PF4MNA 018 High PF4MNA 019 Medium High 1055 PF4MNA 024 High PF4MNA 025 Medium High 1070...
  • Page 11 Table 3 – Electric Heater Static Pressure Drop (in. wc) 018 --- 037 042 --- 061 EXTERNAL STATIC EXTERNAL STATIC HEATER HEATER PRESSURE PRESSURE ELEMENTS ELEMENTS CORRECTION CORRECTION +.02 +.04 3, 5 +.01 8, 10 +.02 8, 10 9, 15 9, 15 –.02 –.02...
  • Page 12: R- -410A Quick Reference Guide

    All indoor coils must be installed with a hard- -shutoff R- -410A refrigerant TXV metering device. Catalog No. IM---PF4M---04 Copyright 2016 Payne Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 . Edition Date: 04/16 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Table of Contents