Payne PY3G Series Product Data
Payne PY3G Series Product Data

Payne PY3G Series Product Data

13 seer single packaged air conditioner and gas furnace system with r-410a refrigerant single and three phase 2-5 nominal tons (sizes 024-060)
Hide thumbs Also See for PY3G Series:

Advertisement

Fig. 1 - - Unit PY3G
Single- -Packaged Products with Energy- -Saving Features and
R- -410A refrigerant.
S Up to 13.5 SEER
S Up to 81% AFUE
S Factory- -Installed TXV
S Multi- -Speed Blower- -Standard
S Direct Spark Ignition
S Low Sound Levels
FEATURES/BENEFITS
One- -piece heating and cooling units with low sound levels, easy
installation, low maintenance, and dependable performance.
Easy Installation
Factory- -assembled package is a compact, fully self- -contained,
combination gas heating/electric cooling unit that is prewired,
pre- -piped, and pre- -charged for minimum installation expense.
These units are available in a variety of standard and optional
heating/ cooling size combinations with voltage options to meet
residential and light commercial requirements. Units are
lightweight and install easily on a rooftop or at ground level. The
high tech composite base eliminates rust problems associated with
ground level applications.
13 SEER SINGLE PACKAGED AIR CONDITIONER AND
GAS FURNACE SYSTEM WITH R- -410A REFRIGERANT

Product Data

Convertible duct configuration
Unit is designed for easy use in either downflow or horizontal
applications. Each unit is easily converted from horizontal to
downflow with the two standard duct covers. Downflow operation
is easily provided in the field to allow vertical ductwork
connections. The basepan utilizes knockout style seals on the
bottom openings to ensure a positive seal in the horizontal airflow
mode.
Efficient operation High- -efficiency design
(Seasonal Energy Efficiency Ratios) of up to 13.5 and AFUE
(Annual Fuel Utilization Efficiency) ratings as high as 80.4%.
Energy- -saving, direct spark ignition saves gas by operating only
when the room thermostat calls for heating. Standard units are
furnished with natural gas controls. A low- -cost field installed kit
for propane conversion is available for all units.
PY3G have dedicated Low NOx units designed for California
installations. These models meet the California maximum oxides of
nitrogen (NOx) emissions requirement of 40 nanograms/joule or
less as shipped from the factory and MUST be installed in
California Air Quality Management Districts where a Low NOx
rule exists. Low NOx option is available on single phase models
only.
A09581
Durable, dependable components Compressors are designed
for high efficiency. Each compressor is hermetically sealed against
contamination to help promote longer life and dependable
operation. Each compressor also has vibration isolation to provide
quieter operation. All compressors have internal high pressure and
overcurrent protection.
Monoport inshot burners produce precise air- -to- -gas mixture,
which provides for clean and efficient combustion. The large
monoport on the inshot (or injection type) burners seldom, if ever,
requires cleaning. All gas furnace components are accessible in one
compartment.
Turbo- -tubulart heat exchangers are constructed of aluminized
steel for corrosion resistance and optimum heat transfer for
improved efficiency. The tubular design permits hot gases to make
multiple passes across the path of the supply air.
In addition, dimples located on the heat exchanger walls force the
hot gases to stay in close contact with the walls, improving heat
transfer.
Direct- -drive high efficiency brushless DC multi- -speed blower
motor is standard on all PY3G models.
Direct- -drive PSC condenser- -fan motors are designed to help
reduce energy consumption and provide for cooing operation
down to 40_F (4.4_C) outdoor temperature. Motormasterr II low
ambient kit is available as a field- -installed accessory.
Thermostatic Expansion Valve - - A hard shutoff, balance port
TXV maintains a constant superheat at the evaporator exit (cooling
cycle) resulting in higher overall system efficiency.
Refrigerant system is designed to provide dependability. Liquid
filter driers are used to promote clean, unrestricted operation. Each
unit leaves the factory with a full refrigerant charge. Refrigerant
service connections make checking operating pressures easier.
1
SINGLE AND THREE PHASE
2- -5 NOMINAL TONS (SIZES 024- - 060)
PY3G
offers SEER

Advertisement

Table of Contents
loading

Summary of Contents for Payne PY3G Series

  • Page 1: Product Data

    A low- -cost field installed kit for propane conversion is available for all units. PY3G have dedicated Low NOx units designed for California installations. These models meet the California maximum oxides of nitrogen (NOx) emissions requirement of 40 nanograms/joule or...
  • Page 2: Table Of Contents

    High and Low Pressure Switches provide added reliability for the Standard metal duct covers with insulation come with the unit compressor. and cover the horizontal duct openings. These can be left in place if the units are converted to downflow. Indoor and Outdoor coils are computer- -designed for optimum heat transfer and efficiency.
  • Page 3: Model Number Nomenclature

    MODEL NUMBER NOMENCLATURE PY3G --- --- Type of Unit PY3G--- Single Packaged Gas Heating/Electric Options Cooling Unit Electrical Supply TP --- Base unit with tin plated indoor coil hairpins N --- 208/230--- 1--- 60 P --- 208/230--- 3--- 60 See Price Page for full list of factory options.
  • Page 4: Ari Capacities

    ARI* CAPACITIES Cooling Capacities and Efficiencies NET COOLING UNIT PY3G NOMINAL TONS STANDARD CFM EER** SEER† CAPACITIES (Btuh) 23,000 11.0 13.2 2- -1/2 1000 28,600 11.2 13.5 1200 34,400 11.0 13.0 3- -1/2 1400 40,500 11.2 13.2 1600 46,500 11.2 13.2...
  • Page 5: Physical Data

    PHYSICAL DATA UNIT SIZE 024040 024060 030040 030060 036060 036090 042060 042090 NOMINAL CAPACITY (ton) 2 ---1/2 2 ---1/2 3 ---1/2 3 ---1/2 SHIPPING WEIGHT** lb. SHIPPING WEIGHT** (kg) Scroll COMPRESSORS Quantity REFRIGERANT (R --- 410A) Quantity lb. Quantity (kg) REFRIGERANT METERING DEVICE OUTDOOR COIL Rows...Fins/in.
  • Page 6: Physical Data 5

    PHYSICAL DATA (CONT) UNIT SIZE 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY (ton) SHIPPING WEIGHT** lb SHIPPING WEIGHT** kg Scroll COMPRESSORS Quantity REFRIGERANT (R --- 410A) Quantity lb 10.0 10.0 10.0 Quantity (kg.) REFRIGERANT METERING DEVICE OUTDOOR COIL Rows...Fins/in. 1...21 1...21 1...21...
  • Page 7: Options And Accessories

    OPTIONS AND ACCESSORIES Compressor start kit assists compressor start- -up by providing additional starting torque on single phase units and prolongs Field- -installed accessories compressor motor life. Economizer with Solid- - State Controls and Barometric Corporate Thermostats provide control for the system heating Relief Dampers and cooling functions.
  • Page 8 ECONOMIZER COIL FILTER ACCESS DOOR (HORIZONTAL APPLICATION ONLY.) FILTER DO NOT REMOVE FROM DOWNFLOW DISCHARGE. REPLACEMENT ECONOMIZER PANEL HOLE FOR ECONOMIZER WIRING HARDNESS 17 13/32 11 13/32” RAINHOOD DOOR CAULK BOTTOM CORNER LATCH ANGLE OF ECONOMIZER 16 1/4” SIDE VIEW ON EACH SIDE HINGED FILTER ACCESS DOOR...
  • Page 9 UNIT DIMENSIONS - - PY3G024- - 036 A08598...
  • Page 10 UNIT DIMENSIONS - - PY3G042- - 060 A08599...
  • Page 11: Accessory Dimensions

    ACCESSORY DIMENSIONS HVAC unit HVAC unit base base Gask eting inner flange* Scre w Scre w Gask eting (NO TE A) (NO TE A) inner flange* *Gask eting *Gask eting outer flange outer flange Wood nailer* Wood nailer* Flashing field Flashing field supplied supplied...
  • Page 12: Selection Procedure

    SELECTION PROCEDURE (WITH EXAMPLE) 1. Determine cooling and heating requirements at 4. Determine fan speed and power requirements at design conditions: design conditions. Given: Before entering the air delivery tables, calculate the total static pressure required. From the given example, the Wet Coil Pressure Required Cooling Capacity (TC) .
  • Page 19: Performance Data

    PERFORMANCE DATA (CONT) * At 75°F (24°C) entering dry bulb---Tennessee Valley Authority (TVA) rating conditions; all others at 80 F (27°C) dry bulb. ° LEGEND BF— Bypass Factor edb— Entering Dry ---Bulb Ewb— Entering Wet---Bulb kW — Total Unit Power Input SHC—...
  • Page 20 PERFORMANCE DATA (CONT) Dry Coil Air Delivery* - - Horizontal and Downflow Discharge - - Unit PY3G024- -060 External Static Pressure (IN. W.C.) Heating Motor Wire Unit Rise Range Speed Color --- --- --- --- --- --- --- --- --- --- Heating Rise ( Blue...
  • Page 21 PERFORMANCE DATA (CONT) Dry Coil Air Delivery* - - Horizontal and Downflow Discharge - - Unit PY3G024- -060 (Cont) External Static Pressure (IN. W.C.) Heating Motor Wire Unit Rise Range Speed Color --- --- --- --- --- --- --- --- --- --- Heating Rise (...
  • Page 22 PERFORMANCE DATA (CONT) Dry Coil Air Delivery* - - Horizontal and Downflow Discharge - - Unit PY3G024- -060 (Cont) External Static Pressure (IN. W.C.) Heating Motor Wire Unit Rise Range Speed Color 1295 1234 1182 1126 1075 1016 Heating Rise ( Blue Heating Rise (...
  • Page 23 PERFORMANCE DATA (CONT) Dry Coil Air Delivery* - - Horizontal and Downflow Discharge - - Unit PY3G024- -060 (Cont) External Static Pressure (IN. W.C.) Heating Motor Wire Unit Rise Range Speed Color 1402 1351 1311 1263 1224 1172 1136 1080 1041 Heating Rise (...
  • Page 24 Rise ( Heating Rise ( * Air delivery values are without air filter and are for dry coil (See PY3G Wet Coil Pressure Drop table). Factory ---shipped heating speed Factory ---shipped cooling speed NA --- Not allowed for heating speed Note: Deduct field---supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
  • Page 25 PERFORMANCE DATA (CONT) PY3G Wet Coil Pressure Drop STANDARD CFM (S.C.F.M) UNIT SIZE 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 0.030 0.037 0.044 0.053 0.063 0.037 0.044 0.053 0.063 0.072 0.081 0.105 0.055 0.060 0.090 0.100 0.110...
  • Page 26: Typical Piping And Wiring

    TYPICAL PIPING AND WIRING ROOF-MOUNTING CURB ROOF RETURN-AIR FLEXIBLE DUCT SUPPLY-AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX (FIELD-SUPPLIED) A09607 INDOOR THERMOSTAT RETURN FROM TOP COVER POWER SOURCE DISCONNECT PER NEC* FROM GAS LINE *NEC - NATIONAL ELECTRICAL CODE A09608...
  • Page 27: Application Data

    APPLICATION DATA Maximum cooling airflow — To minimize the possibility of Condensate trap — A 2- -in. (51 mm) condensate trap must be condensate blow- -off from the evaporator, airflow through the units field supplied. should not exceed 450 cfm per ton. Ductwork —...
  • Page 28: Electrical Data

    ELECTRICAL DATA NOMINAL VOLTAGE RANGE COMPRESSOR POWER SUPPLY UNIT V- -PH- -HZ MOCP** PY3G024040 12.8 58.3 21.3 PY3G024060 12.8 58.3 21.3 PY3G030040 12.8 64.0 21.3 PY3G030060 12.8 64.0 21.3 PY3G036060 16.7 79.0 28.0 PY3G036090 16.7 79.0 28.0 PY3G042060 17.9 112.0 29.6 208/230--1--60 PY3G042090...
  • Page 29 TYPICAL WIRING SCHEMATIC 208/230- -1- - 60 A08052...
  • Page 30 TYPICAL WIRING SCHEMATIC 208/230- -3- - 60 A08053...
  • Page 31 TYPICAL WIRING SCHEMATIC 460- -3- -60 A08010...
  • Page 32: Controls

    CONTROLS On the loss of the thermostat call for cooling, 24 V is removed Operating sequence from both the “Y” and “G” terminals (provided the fan switch is in Heating - - On a call for heating, terminal W of the thermostat is the “AUTO”...
  • Page 33: Guide Specifications

    40,000 to 130,000 Btuh, dynamically balanced, and discharge air vertically. Nominal Heating Input D. Compressor: Model Number: PY3G 1. Fully hermetic compressors with factory- -installed vibration Part 1 — General isolation. SYSTEM DESCRIPTION 2.
  • Page 34 (0 to 2000 ft [0 to 610 m] above sea compressors. level). Catalog No: SS---PY3G ---02 E2009 Payne Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 11/09 Replaces: NEW Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.