Fireye BurnerLogiX ZB110 Manual page 76

Table of Contents

Advertisement

®
Flame Signal Strength
Routine observation of the flame signal strength will forewarn any deterioration in the capability of
the flame detector or its application.
Contacts
There are no accessible contacts in the BurnerLogix. Where contacts are used, their design assures
long trouble-free life when the load circuits are maintained within the published load ratings.
Humidity
In areas of high humidity, the control chassis should be removed and placed in a dry atmosphere
when the system is expected to be out of service for an extended period.
Periodic Safety Check
It is recommended that a procedure be established to test the complete flame safeguard system at
least once a month,. This test should verify the proper operation of all limit switches and safety inter-
locks as well as flame failure protection and fuel safety shutoff valve tightness.
Rotation
It is recommended that control and scanner units purchased as spares be installed periodically to
ensure proper operation.
76

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Fireye BurnerLogiX ZB110

This manual is also suitable for:

Burnerlogix zb230Burnerlogix bll510Burnerlogix blv512

Table of Contents