Fireye BurnerLogiX ZB110 Manual page 23

Table of Contents

Advertisement

Modifiable parameters located in PROGRAM SETUP MENU
Parameter
Factory Default
Purge time
00:30s
Count method
DOWN
Prove 3-P open at start
PTFI*MTFI timing
10/10*10/15
YP113 = 5/5*3/5
Terminal 6 interrupted
INTRP
or intermittent
Prove M-8 open
Prove M-D open
Post purge
M-D WAIT 10m
PROVE M-D TFI
Baud rate
Unit address
Lock Settings
DO IR LEARN
Shaded parameters not affected by 8 hour burn-in or LOCK SETTINGS.
All programmed settings become permanent if the BurnerLogix system has been powered
continuously and 8 hours of main burner (terminal 7) on time has been accumulated. If the
AC power is removed prior to accumulating 8 hours of main burner on time, the system
burn-in time clock will be reset to zero. It is not necessary for the main burner on time to be
continuous. The BurnerLogix accumulates burner on time in seconds. If necessary, the pro-
grammed settings can be made to become permanent anytime before the required 8 hours of
main burner on time through the use of the optional keypad and the LOCK SETTINGS
option under the PROGRAM SETUP sub menu.
Refer to SYSTEM INFO Sub Menu, page 49, for language selection.
Range
0:30s – 60:00m, 15 second
increments.
0:10s-60:00m, YP113
0:00s-60:00m, YP115
(0:00s - 60:00m in YP3XX)
UP, DOWN
NO
YES, NO
See chart page 18
INTRP, INTMT
NO
YES, NO
NO
YES, NO
0:15
0:15s - 1:00m, 5 second
increments.
YES
YES, NO
NO
YES, NO
9600
4800, 9600, 19200, 38400
00
00-31
NO
YES, NO
NO
YES, NO
®
Description
Applies to open damper purge time in YP1XX and YP2XX pro-
grammers and to low fire start time in YP3XX programmers.
Time counts UP to final value or DOWN to zero from starting
value. This setting will apply to all timer values.
Prevents jumped terminals. Requires the 3-P circuit to be
open at the start of a cycle.
Applies to terminals 5 and 6 operation during PTFI and MTFI.
Provide interrupted or intermittent operation on terminal 6.
If YES, M-8 must be open at start of open damper purge
period. (YP1XX Series only).
If YES, M-D must be open at end of open damper purge
period. Does not apply to YP3XX Series.
Selects Post Purge time.
Select YES for lockout on M-D open for 10 minutes. Select
NO for indefinite wait for M-D to close. This wait time applies
prior to pilot trial for ignition.
Select YES to force lockout on M-D opening during PTFI and
MTFI.
Sets communication baud rate
Multi-drop requires unique addressing. Lowest address
allowed for modbus is 01
Parameters can be stored to memory before automatic 8 hour
store.
Select YES to activate IR LEARN process. See IR operation.