If no well connection is provided, select an appropriate location for mounting the temperature
sensor. Preferably as close to the boiler outlet as possible.
OUTDOOR TEMPERATURE
1.
The outdoor air temperature sensor should be mounted on the outside of the building where it
will be exposed to representative air temperature, but not to direct sunlight. A sun shield may be
required.
2.
Mount the temperature sensor high enough so it cannot be covered with snow, leaves, or other
debris, or be tampered with. Vents from the building should be avoided
WIRING PRESSURE AND TEMPERATURE SENSORS
CAUTION: Disconnect power supply from the BurnerLogix Control before connecting
wires to prevent electrical shock and equipment damage.
1.
All wiring must be in accordance with National Electrical Code and local codes, ordinances, and
regulations.
2.
Sensor housing provides connection for 1/2" conduit.
3.
The pressure and temperature sensors require 2 conductor, 18 gauge, shielded cable. Power lim-
ited, rated for 300V @105C. Use Belden 9318 or equivalent.
4.
The shield should be connected to the earth ground terminal on the wiring base of the Burner-
Logix Control (Terminal #E). The shield should be taped at the sensor to avoid unintended con-
tact with the sensor housing.
5.
All sensor wiring should be in a separate conduit. DO NOT install sensor wiring in any conduit
or junction boxes with high voltage wiring.
6.
Maximum wiring distance for sensor wiring is 100 feet.
7.
See following chart for wiring terminations:
TS350/TS752
1
2
CAUTION: PROGRAM AND SET-UP
The proper operation of the BurnerLogix System and the pressure and temperature sensors
require that the selected pressure ranges are appropriate for the application and must
match the pressure range programmed on the BurnerLogix Control. Insure that the range
of the selected sensor is correct for the application and pressure range matches the installed
pressure sensor.
WIRING FIRING RATE MOTOR
1.
All wiring must be in accordance with National Electrical Code and local codes, ordinances, and
regulations.
2.
For 4-20 mA motors, use 2 conductor, 18 gauge, shielded cable. Power limited, rated for 300V
@105C. Use Belden 9318 or equivalent.
3.
The shield should be connected to the earth ground terminal on the wiring base of the Burner-
Logix Control (Terminal #E). The shield should be taped at the motor to avoid unintended con-
tact with the motor housing.
4.
All wiring should be in a separate conduit. DO NOT install wiring in any conduit or junction
boxes with high voltage wiring.
5.
Maximum wiring distance for sensor wiring is 100 feet.
BLPS
PCV
+EXC
X (WHT/BLU)
-COM
11 (WHT/GRN)
®
AUX1
X (WHT/BLU)
X (WHT/BLU)
22 WHT/VIO)
23 (BRN/WHT)
AUX2
15