Fault Record Structure Header - ABB RER615 Modbus Point List Manual

Grid automation recloser protection and control
Hide thumbs Also See for RER615:
Table of Contents

Advertisement

Section 2
Modbus data mappings
RegA
Type
Scale
9351
u16
1
9352
u16
1
9353
u16
1
9354
u16
1
9355
u16
1
9356
u16
1
9357
u16
1
9358
u16
1
9359
u16
1
9360
u16
1
9361
u16
1
1) See the technical manual.
2.4.50
Table 141:

Fault record structure header

RegA
Type
Scale
9401
u16
9402
u16
9403
u16
9404
u16
9405
u16
9406
u16
9407
u16
9408
u16
9409
u16
100
9410
u16
1
9411
u16
100
9412
u16
9413
u16
9414
u16
9415
u16
Table continues on next page
76
IEC 61850 name
Fault record structure header
IEC 61850 name
LD0.FLTMSTA1
.StrDur.mag
.ActSG.stVal
.FltDiskm.mag
SA name
Description
Record 10 data to read:
- Record sequence num
- Unread records left
Timestamp of record
- Year, Month
- Day, Hour
- Minute, Second
- Millisecond
Event identification
Data object ID1
Data object ID2
Event data value 1
Event data value 2
SA name
Description
Selection write:
- Read selection
Record data header:
- Record sequence num
- Unread records left
Timestamp of record:
- Year, month
- Day, hour
- Minute, second
- Millisecond
- Timestamp quality
- Start duration
- Active setting group
- Fault distance
< reserved >
< reserved >
< reserved >
< reserved >
1MRS757822 B
Values
If selected
1...9999
0...499
Year/Month
Day/Hour
Min/Sec
Millisecond
1)
1)
1)
1)
1)
Values
-99...3
0...65535
0...99
Year/Month
Day/Hour
Min/Sec
Millisecond
1)
0...100.00 [%]
1...6
0...9999.99
[pu]
0
0
0
0
Recloser Protection and Control RER615
Point List Manual