Section 2
Modbus data mappings
2.3.17
Table 20:

LD0.EFPADM3 Admittance-based earth-fault protection (3)

BitA
RegA
2860
178.12
2861
178.13
2862
178.14
2863
178.15
2.3.18
Table 21:

LD0.WPWDE1 Wattmetric-based earth-fault protection (1)

BitA
RegA
3296
206.00
3297
206.01
3298
206.02
3299
206.03
2.3.19
Table 22:

LD0.WPWDE2 Wattmetric-based earth-fault protection (2)

BitA
RegA
3300
206.04
3301
206.05
3302
206.06
3303
206.07
2.3.20
Table 23:

LD0.WPWDE3 Wattmetric-based earth-fault protection (3)

BitA
RegA
3304
206.08
3305
206.09
3306
206.10
3307
206.11
24
LD0.EFPADM3 Admittance-based earth-fault protection (3)
IEC 61850 name
SA name
LD0.EFPADM3
.Str.general
START
.mcd
.Op.general
OPERATE
.mcd
LD0.WPWDE1 Wattmetric-based earth-fault protection (1)
IEC 61850 name
SA name
LD0.WPSDE1
.Str.general
START
.mcd
.Op.general
OPERATE
.mcd
LD0.WPWDE2 Wattmetric-based earth-fault protection (2)
IEC 61850 name
SA name
LD0.WPSDE2
.Str.general
START
.mcd
.Op.general
OPERATE
.mcd
LD0.WPWDE3 Wattmetric-based earth-fault protection (3)
IEC 61850 name
SA name
LD0.WPSDE3
.Str.general
START
.mcd
.Op.general
OPERATE
.mcd
Description
Stage start
Stage operate
Description
Stage start
Stage operate
Description
Stage start
Stage operate
Description
Stage start
Stage operate
Recloser Protection and Control RER615
1MRS757822 B
Values
1=Start
1=Operate
Values
1=Start
1=Operate
Values
1=Start
1=Operate
Values
1=Start
1=Operate
Point List Manual