Ld0.Mdsopt1 Generic Operation Time Supervision; Ld0.Cmmxu1 Phase Current Measurements (1); Ld0.Cmsqi1 Sequence Of Current Measurements (1); Ld0.Rescmmxu1 Residual Current Measurement (1) - ABB RER615 Modbus Point List Manual

Grid automation recloser protection and control
Hide thumbs Also See for RER615:
Table of Contents

Advertisement

1MRS757822 B
2.4.17
Table 108:

LD0.MDSOPT1 Generic operation time supervision

RegA
Type
Scale
2048
u16
1
2.4.18
Table 109:

LD0.CMMXU1 Phase current measurements (1)

RegA
Type
Scale
138
u16
1000
139
u16
1000
140
u16
1000
2.4.19
Table 110:

LD0.CMSQI1 Sequence of current measurements (1)

RegA
Type
Scale
143
u16
1000
144
u16
1000
145
u16
1000
2.4.20
Table 111:

LD0.RESCMMXU1 Residual current measurement (1)

RegA
Type
Scale
141
u16
1000
Recloser Protection and Control RER615
Point List Manual
LD0.MDSOPT1 Generic operation time supervision
Since the register size is 16 bits, the value saturates at 65535 hours (approximately
7.5 years). Alternatively, a 32-bit user-definable register can be made of this data to
cover the whole 300 000 hours (34 years) range. The value can also, for example,
be rescaled to show "total operation days" instead by changing the scale factor
from 1 to 1/24 = 0.0417.
IEC 61850 name
.stVal
LD0.CMMXU1 Phase current measurements (1)
IEC 61850 name
LD0.CMMXU1
.A.phsA.instCVal.mag
.A.phsB.instCVal.mag
.A.phsC.instCVal.mag
LD0.CMSQI1 Sequence of current measurements (1)
IEC 61850 name
LD0.CMSQI1
.SeqA.c1.instCVal.mag
.SeqA.c2.instCVal.mag
.SeqA.c2.instCVal.mag
LD0.RESCMMXU1 Residual current measurement (1)
IEC 61850 name
LD0.RESCMMXU1
.A.res.instCVal.mag
SA name
Description
OPR_TIME
Operating hours
SA name
Description
Phase current (1)
I_INST_A
- phsA amplitude
I_INST_B
- phsB amplitude
I_INST_C
- phsC amplitude
SA name
Description
Sequence of currents
I1_INST
- positive amplitude
I2_INST
- negative amplitude
I3_INST
- zero amplitude
SA name
Description
Residual current (1)
I0_INST
- amplitude
Section 2
Modbus data mappings
Values
0...299999
[hours]
Values
0.00...40.0
[xIn]
0.00...40.0
[xIn]
0.00...40.0
[xIn]
Values
0.00...40.0
[xIn]
0.00...40.0
[xIn]
0.00...40.0
[xIn]
Values
0.00...40.0
[xIn]
61

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615