Indications - ABB RER615 Modbus Point List Manual

Grid automation recloser protection and control
Hide thumbs Also See for RER615:
Table of Contents

Advertisement

1MRS757822 B
Function
Minimum pulse timer (2 pcs)
Minimum pulse timer (2 pcs, second resolution)
Minimum pulse timer (2 pcs, minute resolution)
Pulse timer (8 pcs)
Time delay off (8 pcs)
Time delay on (8 pcs)
Set reset (8 pcs)
Move (8 pcs)
Generic control point (16 pcs)
Remote generic control points
Local generic control points
Generic up-down counters
1, 2, ... = number of included instances
() = optional
1) All directional protection functions can also be used in the non-directional mode
2) The instances of a protection function represent the number of identical protection function blocks available in the standard configuration
3) Only one can be ordered as an option at a time with OC or directional OC
4) Can be ordered as an option when OC is also chosen
5) Io selectable by parameter, Io measured by default
6) Can be ordered as an option when OC or directional OC is also chosen
7) Uo calculated is always used
8) One of the three can be ordered as an option when directional OC and directional EF are chosen: Admittance based EF, Wattmetric
based EF or Harmonics based EF
9) Uo calculated is always used with the first instance
10) UoB calculated is always used with the second instance
11) Voltage group B is always used with the third instance
12) Voltage group B is always used with the second instance
2.3
Recloser Protection and Control RER615
Point List Manual

Indications

Table 3:
Explanations of the indications table columns
Column name
Description
BitA
Default 0X and 1X bit address for the data.
RegA
Default 3X and 4X register.bit (00-15) address for the data.
IEC 61850
Original IED data object identification. Described in the IEC 61850 format as
name
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name
The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description
Short description of the signal. See the technical manual for more information.
Value
Meaning of the value states.
Section 2
Modbus data mappings
IEC 61850
A
RE01
TPGAPC
2
TPSGAPC
1
TPMGAPC
1
PTGAPC
2
TOFGAPC
2
TONGAPC
2
SRGAPC
2
MVGAPC
2
SPCGGIO
2
SPCRGGIO
1
SPCLGGIO
1
UDFCNT
3
D
RE02
2
1
1
2
2
2
2
2
2
1
1
3
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615

Table of Contents