Serial Communication Analog Value Data
This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1025 + AV #.
TABLE 44 - SERIAL COMMUNICATION ANALOG VALUE DATA
AV
BACNET NAME
1
REM_SETP
2
SP_REM_SP_S1
3
LOAD_LIMIT
4
REM_CR
5
SP_REM_SP_S2
6
REM_SP_HEAT
7
HP_MODE
Serial Communication Binary Value Data
This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1537 + BV #.
TABLE 45 - SERIAL COMMUNICATION BINARY VALUE DATA
BV
BACNET NAME
1
START_STOP
2
SS_SYS1
3
SS_SYS2
Serial Communication Analog Input Data
This data can be read using a BACnet or Modbus net-
work connection and can NOT be modified using this
connection. The Modbus Register Address for these
points is 513 + AI #.
TABLE 46 - SERIAL COMMUNICATION ANALOG INPUT DATA
AI
BACNET NAME
1
LCHLT
2
RCHLT
3
DAT
4
S1_SUCT_TEMP
5
OAT
6
S1_SUCT_SH
7
S1_RUN_TIME
8
S1_SUCT_PR
9
S1_DSCH_PR
10
S1_CIR_TEMP
JOHNSON CONTROLS
ANALOG VALUE DESCRIPTION
Setpoint
Cooling Setpoint (HP Only), 99 = Auto
(40 °F - 70 °F)
SYS 1 Setpoint (Suction Pressure Control)
Load Limit Stage (0, 1, 2)
Cooling Range (DAT Mode Only)
SYS 2 Setpoint (Suction Pressure Control)
Heating Setpoint (HP Only) 99 = Auto (95 °F - 122 °F)
Mode (HP Only) (0 = Panel, 1 = Cooling, 2 = Heating)
BINARY VALUE DESCRIPTION
Start / Stop Command
SYS 1 Start / Stop Command (Suction Pressure Control)
SYS 2 Start / Stop Command (Suction Pressure Control)
ANALOG INPUT DESCRIPTION
Leaving Chilled Liquid Temp
Return Chilled Liquid Temp
Discharge Air Temp (Cond Unit Only)
SYS 1 Suction Temperature (EEV And Cond Unit Only)
Ambient Air Temperature
SYS 1 Suction Superheat (EEV Only)
SYS 1 Run Time (Seconds)
SYS 1 Suction Pressure
SYS 1 Discharge Pressure
SYS 1 Cooler Inlet Refrigerant Temperature (R-407C Only)