3.6 LL: S1+S2 dialing setting error (for MS04-12)
Digital display output
Description
S1+S2 dialing setting error.
All units stop running.
Error code is displayed on the malfunction MS box.
The indoor unit display board or wired controller connected to this MS displays "F8".
Trigger / recover condition
Trigger condition: S1 and S2 are set to ON, but the indoor unit is connected to both pipes 1 and 2 (or the indoor unit is
connected to pipes 3 and 4).
Recover condition: Does not meet trigger conditions.
Reset method: Manually restart.
Possible causes
S1+S2 dialing setting error.
Signal cables are incorrectly connected.
MS PCB damaged.
Procedure
S1+S2 dialing setting error.
Signal cable is incorrectly connected
Replace the MS main PCB
LL
No
No
Yes
Reset dial S1+S2.
Check and connect the signal cables
Yes
properly.
V6R VRF 50/60Hz
155