Download Print this page
Veris Industries H5004 Installation Manual

Veris Industries H5004 Installation Manual

Current sensing four-point remote status panel/sensor ki

Advertisement

Quick Links

H5004/H5004C
H5004
proDuct iDEntification
Model
H5004
Remote Status Panel
H5004C
Remote Status Panel Kit (includes four H5800 current sensors)
H5800
Current Sensors, sold separately
Wiring ExamplE
Motor
Control Center
Digital Control
Digital
Status
Inputs
Hawkeye 5000
Adjustable Current
Status Sensor
Z201171-0A
PAGE 1
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
CURRENT MONITORING
H5004C
Description
Fan/pump #1
Fan/pump #2
Starters
H5800 Mini-Sensor
©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com
INSTALLATION GUIDE
Current Sensing Four-Point
Remote Status Panel/Sensor Kit
Installer's Specifications
Temperature Range
Humidity Range
Trip Point
Hysteresis
Output Type
Output Rating
No. of Points Accepted
Supply Voltage
Supply Current
Housing
H5800 Current Sensor:
Amperage Ratings
Wiring
All outputs and adjustments are per point.
Do not use the LED status indicators as evidence.
quick install
1.
Disconnect and lock out power to the conductor to be monitored.
2.
Install the Remote Status Panel near the controller. Wire the supply voltage
terminal to 24VAC/DC power source.
3.
Slide the conductors to be monitored through the sensing irises of the current
transducers (up to 4 transducers per Panel). See Notes (page 2) for currents under
1 Amp or above 100 Amp. Note: Transducers may be located up to 1000 feet from
the Remote Status Panel.
4.
Wire the output connections between the sensors and the Remote Status Panel.
See Wiring section (page 2) for details. Sensors are polarity sensitive.
5.
Adjust the amperage setpoint at which the Panel output will trip. Turn clockwise
to increase.
6.
Reconnect power.
DimEnsions
4.2"
(105 mm)
2.75"
(70 mm)
5004/5004C
-15° to 85°C (5° to 185°F)
0 - 95% non-condensing
Dry Contact, reed relay, N.O.
200mA@30VAC/DC
50mA@120VAC
1-4 sensors (H5800 solid core)
1 to 100A continuous
Up to 1000' from panel, 2 wire, 22 AWG twisted pair
Ø = 0.7"
(18 mm)
0.9"
(22 mm)
2.3"
(58 mm)
1.8"
(46 mm)
Adjustable
10% Typical
24VAC/DC
50mA max.
NEMA 1
2.5"
(64 mm)
09083

Advertisement

loading

Summary of Contents for Veris Industries H5004

  • Page 1 Z201171-0A PAGE 1 ©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com 09083 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
  • Page 2 Z201171-0A PAGE 2 ©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / support@veris.com 09083 Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

This manual is also suitable for:

H5004cH5800