Installation

To install backbox and micro-DAU PCB
Mount the backbox to a flat wall surface using
suitable fixings. Fit the micro-DAU PCB into the
backbox using the fixing screw and washer provided.
&
When fitting micro-DAU PCB into the
backbox ensure the spring on the bottom edge of
the board engages into the spring stop and the
bottom edge of the board fits under the retaining
clips.
micro-DAU
PCB
PCB clip-on points
PCB fixing point use
screw and washer supplied
Bottom PCB
retaining clip
Spring-switch
To discharge amplifier energy on removal
of PCB from backbox
Removable terminal block
For ease of wiring the micro-DAU, the terminal blocks
on the PCB can be unplugged.
Removable
WEEE Directive:
At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.
Do not dispose of with your normal household waste.
Do not burn.
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without
obligation to notify any person of such revisions of changes.
by Honeywell
Back box
Bottom PCB
retaining clip
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK
Telephone: +44 (0) 116 246 2000
micro Distributed Amplifier Unit
Terminals for external wiring
The micro-DAU has terminals for the connection of
device loop circuit, audio loop circuit, speaker
circuits, local audio (for local background music) and
local test microphone.
&
Always connect the micro-DAU on the
MAIN DEVICE LOOP (analogue loop) and not on a
Spur circuit off the main loop.
There MUST be at least one speaker connected to
each speaker circuit.
.
L1 01 L2 02
P4
LOOP
B
A
0V
P6
LOCAL
AUDIO
L1 01 L2 02
A
B
0V
BLK
P4
P6
LOOP
LOCAL
AUDIO
MICROPHONE
P2
P17
I/R SENSOR
P9
Audio
Status
P9
A-CCT
B-CCT
SW2
SW1
ENSURE
CAL
SPRING
FITTED
P17
"
After all the wiring is complete fit the bungs
supplied in the spares pack to cover up the unused cable
entry holes. Close the outer door and use the socket head
screws to lock the door.
For details on wiring, see the Vigilon Compact Voice
Alarm Installation instructions booklet supplied with
the control panel.
At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.
Tech. Support: www.gentexpert.co.uk
4188-781 issue 6_Part 1_08/10_micro DAU install
N01 C1 NC1 NO2 C2 NC2
I/A I/B O/A O/B
AUX RELAY CONTACTS
P3
AUDIO
A+ A- B+ B-
LOOP
P2
SPEAKERS
RED
GN
WH
I/A I/B O/A O/B
N01 C1 NC1 NO2 C2 NC2
A+ A- B+ B-
P5
P3
P1
P11
AUDIO LOOP
AUX RELAY CONTACTS
LD1
L3
L4
DISCHARGE
LED
During commissioning this link must
be removed from connector P17. The
link must be replaced after
commissioning the micro-DAU.