Veris Industries Hawkeye 8025 Installation Instructions Manual page 5

Networked (n2 bus) power meter
Table of Contents

Advertisement

POINT MAP FOR H8026 ENERGY METER ENHANCED DATA STREAM, N2 PROTOCOL
Johnson Controls N2 OPEN, "VND" TYPE
NPA
UNITS
NPT
1
BI
kWH
kW
(see Note 1)
1
AI
kWH
AI
2
kW
kVAR
3
AI
4
kVA
AI
5
AI
AI
kW
6
7
kW
AI
AI
8
kW
Volts
AI
9
AI
Volts
10
AI
11
Amps
12
kW
AI
13
AI
kW
14
AI
kW
15
AI
AI
16
AI
17
18
AI
Volts
19
Volts
AI
AI
20
Volts
AI
21
Volts
AI
22
Volts
AI
23
Volts
24
AI
Amps
25
Amps
AI
26
Amps
AI
ADI
1
ADI
2
BO
1
BO
2
NPT = Network Point Type
NPA = Network Point Address
Note 1: Phase A corresponds to the Red Lead. Phase B corresponds to the Black Lead. Phase C corresponds to the Yellow Lead.
POINT DESCRIPTION
Consumption (Accum)
Consumption
Real Power
Reactive Power
VA (apparent power)
Power Factor, total
Average Real Power
Minimum Real Power
Maximum Real Power
Voltage, Line to Line
Voltage, Line to Neutral
Current
Real Power, Phase A
Real Power, Phase B
Real Power, Phase C
Power Factor, Phase A
Power Factor, Phase B
Power Factor, Phase C
Voltage, Phase A-B
Voltage, Phase B-C
Voltage, Phase A-C
Voltage, Phase A-N
Voltage, Phase B-N
Voltage, Phase C-N
Current, Phase A
Current, Phase B
Current, Phase C
Preset kWH, LSW
Preset kWH, MSW
Reset kWH
Reset Min/Max/Avg
RANGE/VALUE
100A: 0.0025 kWH/count
300A: 0.01 kWH/count
400A: 0.01 kWH/count
800A: 0.02 kWH/count
1600A: 0.04 kWH/count
2400A: 0.08 kWH/count
100A: 0 to 10737418.24
2400A: 0 to 343597383.7
100A: 0 to 83.1
2400A: 0 to 1995.3
100A: 0 to 83.1
2400A: 0 to 1995.3
100A: 0 to 83.1
2400A: 0 to 1995.3
0 to 1.0
100A: 0 to 83.1
2400A: 0 to 1995.3
100A: 0 to 83.1
2400A: 0 to 1995.3
100A: 0 to 83.1
2400A: 0 to 1995.3
0 to 480
0 to 277
100A: 0 to 100
2400A: 0 to 2400
100A: 0 to 27.7
2400A: 0 to 664.8
100A: 0 to 27.7
2400A: 0 to 664.8
100A: 0 to 27.7
2400A: 0 to 664.8
0 to 1.0
0 to 1.0
0 to 1.0
190 to 480
0 to 480
0 to 480
0 to 277
0 to 277
0 to 277
100A: 0 to 100
2400A 0 to 2400
100A: 0 to 100
2400A 0 to 2400
100A: 0 to 100
2400A 0 to 2400
-32768 to 32767
-32768 to 32767
0=NA, 1=Reset kWH
0=NA, 1=Reset min/max/avg
- 5 -
NOTES
BI-1 is intended to be used as an accumulator (ACM) type,
it should not be read as a binary status.
Allows direct view of kWH accumulator as an AI point. For large
values, BI-1 gives higher precision.
Reads the effective power factor for all phases, which is not an
average of AI-15, AI-16, AI-17.
Reads the average Real Power (kW). This is intended for demand
window applications, where this point is read at the end of each win-
dow, and then reset (via BO-2) to begin the next demand window.
Reads the minimum Real Power since it was reset (via BO-2).
Real Power is internally monitored in 200 ms windows.
Reads the maximum (peak) Real Power since it was reset (via
BO-2). Peak real power is internally monitored in 200 ms windows,
allowing 200 ms peaks to be captured accurately.
Reads the average line to line voltage. Individual voltages are
available in AI-18, AI-19, AI-20
Reads the average line to neutral voltage. Individual voltages
are available in AI-21, AI-22, AI-23
Reads the current. Individual currents are available in AI-24,
AI-25, AI-26
The meter obtains its power from A-B voltage, and it will not
operate at low voltages.
Allows the lower 16 bits of the kWH accumulator to be preset
Allows the upper 16 bits of the kWH accumulator to be preset
Causes the kWH accumulator to be reset to zero. The value will
return to "off". Should not be defined as auto restorable. (see
Note 2)
This point should be commanded to "on" to reset the AI-5, AI-6
and AI-7. The value will return to "off". Should not be defined as
auto restorable. (see Note 2)