9 PLACING INTO OPERATION

To place a correctly installed 4020 FIP into operation perform the following steps:
STEP 1
Ensure that the mains isolate switch is OFF and batteries are
disconnected.
STEP 2
Ensure that 240V AC supply is connected to the panel from the mains
distribution board.
STEP 3
Turn the panel mains isolate switch ON . The panel sounder will start
beeping and the Fault LED will be flashing and the following POWER-UP
message will be displayed:
Press the ACKNOWLEDGE key to silence the sounder and check the
status of the following:
-
-
-
-
STEP 4
Next the fault sounder will start beeping to indicate a battery fault. Press
the ACKNOWLEDGE key to silence the buzzer and acknowledge the
fault.
Now adjust the battery charger float voltage as per section 9.1
STEP 5
Perform a lamp test by pressing the LAMP TEST key.
STEP 6
Perform an alarm test by pressing the ALARM(ALM) TEST key.
Acknowledge each alarm and then press the RESET key to reset the
alarm zone circuits.
ALM
ACK+
TEST
Document No: 4020-M010
** WARNING - CPU RESET HAS OCCURRED **
PRESS ANY KEY TO SILENCE SOUNDER
PWR ON LED indicator is illuminated.
BELL ISOLATED indicator is illuminated.
ACF ISOLATED indicator is illuminated.
Display is in normal display mode ie:
SIMPLEX AUSTRALIA - Time of day - Bat: OK
Alarms: 00 Faults: 00
4
5
RST
1st February, 1997
Isolated : 00
Issue 2.0