Walktest Mode - Simplex 4020 Operating Manual

Fire indicator panel
Table of Contents

Advertisement

Page 36

8.7 WALKTEST MODE

The WALKTEST feature allows one person to perform a complete test of the fire
detectors connected to the 4020 panel. The WALKTEST incorporates an
Acknowledge/Auto Reset feature which allows one person to test the 4020 Fire Alarm
System without the need for another person to be stationed at the control panel to
acknowledge and reset alarm conditions
STEP 1
From the normal display, press the MENU(0) key, the
displayed:
0
MENU
STEP 2
Press KEY 5 to select option 5-Next Menu, the following is displayed:
5
RST
STEP 3
Press the KEY 1 to enable the Walktest mode Walk Test option and the
following is displayed:
1
ALM LIST
STEP 4
Press the MENU(0) key, to activate the Walk Test Mode and the following
is displayed:
0
MENU
Document No: 4020-M010
0-Edit Point, 1-Program ACF, 2-Time/Date
3-Brigade, 4-Prog Mimic, 5-Next Menu
0-2120/Printer, 1-Walk Test, 2-Version
3-Set Passcode, 4-Previous Menu
Press 0 to activate Walk Test
Test will timeout 30 mins after last Alm
*** ALARM WALK TEST IN PROGRESS ***
Alarms:00
Faults:00
1st February, 1997
Isolated : 00
Auto
following is
Issue 2.0