64 bits per card ID. This allows the use of many proprietary Wiegand cards without the need for data conversion. The readers can be Cansec’s CanProx One Proximity Readers (AWID or HID card technology) or one of many other popular Wiegand readers.
See power supply notes in Appendix section for more information. Suggested Power Supply CA-EFLOW4N8D or CA-EFLOW6N8D or CA-EFLOW102N16D……. (see Appendix) MAPMINI Controller Power Requirements Max. Current (including 1 proximity reader with 100 mA)…..12VDC/1A Temperature Range Operating ……………………………………………………………………………… 0˚C to 60˚C Relative Humidity Operating ………………………………………………………..………………………...
Page 5
NOTE: Consult reader specifications as 12-gauge wire may be required for power. Dimensions & Weight MAPMINI Controller………….……………………………4.6” (W) x 3.35” (L) x 1.5” (D) [11.6 cm (W) x 8.5 cm (L) x 3.8 cm D)] MAPMINI Enclosure …………………………………………..9.5" (W) x 13" (L) x 3" (D) [24.0 cm (W) x 33.0 cm (L) x 7.5 cm (D)]...
Page 6
Cansec accepts no responsibility for direct or consequential damages resulting from the failure of emergency lockdown functions which are dependant in any way on the operation of card readers, access control panels, communications networks, communications devices or host software.
MAPMINI Controller Layout Figure 1 MAPMINI Page 7 of 28 Installation Manual September 2021 • Rev. 1.4...
Page 8
Important Installation Notes Controller Provisioning Options: The MAPMINI controller is provisioned with the default 1-door configuration. The MAPMINI can run only in one mode either First Access, Webster or CloudACS. The MAPMINI can be provisioned in one of the two options below: 1.
Page 9
Network Information: 1. The MAPMINI Controller is set to acquire an IP address automatically (DHCP). However, it can be optionally set to a static IP address or reset if necessary. See Appendix section for more information. Mechanical Information: 1. If required, the MAPMINI may be mounted inside of a lockable enclosure such as the CA-SLBOX if access is to be limited to the external connections.
However, it may be more cost effective to use a separate power supply (battery backed-up) just for the MAPMINI Controller and a separate power supply which can be sized to supply the amount of current that the attached high-current device e.g.
ENTRY READER WIRING The first diagrams show entry reader wiring only. The second diagram shows optional exit reader wiring along with the entry reader. Figure 6 Exit reader option must also be enabled in ENTRY AND EXIT READER WIRING the host software. To avoid electrical noise, exit reader...
EXIT BUTTON AND DOOR CONTACT WIRING Note: Both door contact and exit button inputs have voltage present on the circuits. Only connect dry contact devices to these inputs. Figure 8 The RTE/REX can be set to “Normally Open” or “Normally Closed”...
LOCK OUTPUT AND MULTI-FUNCTION RELAY WIRING Electric Strike Lock Wiring – Up To 6 Amp, 30VDC MAX Figure 10 See Note 2 in Appendix section for 6 Amp relay rating The Multi-Function (MF) relay is configured by the user through the host software. This relay can be set to only one of the following options: ...
Page 14
Magnetic Lock Wiring – Up To 6 Amp, 30VDC MAX IMPORTANT: In some jurisdictions, the use of a UL approved power supply and connection to the fire alarm system for emergency release may be required. Installers should contact the local authority having jurisdiction to verify the specific requirements.
INPUT AND OUTPUT POINT WIRING The MAPMINI can be provisioned for all I/O which allows for 2 input points and 2 output points to be used. There is no door provisioned in this mode. Input Wiring – Supervised or Non-Supervised Figure 12 MAPMINI Page 15 of 28...
Page 16
Output Wiring Figure 13 MAPMINI Page 16 of 28 Installation Manual September 2021 • Rev. 1.4...
Appendix Note 1: Suggested Power Supplies & Backup Battery Part Number Dimension & Weight Description H x W x D approx. 13.5” x 13” x 3.25” 12/24 VDC selectable output, CA-EFLOW4N8D 4 Amp Enclosure Style Power (342.9mm x 330.2mm x Supply with Backup Battery 82.55mm) Charger.
Note 2: 6 Amp Relay Rating Maximum current that can be switched reliably when connected to a ‘non-inductive load’ up to 30VDC. Electric strikes and magnetic locks are considered ‘inductive loads’. It is important to have diode or MOV attached at the locking device to remove the CEMF pulse that is generated when switching an ‘inductive load’.
POWER CONNECTOR Figure 14 SHUTDN – SHUTDOWN BUTTON As the MAPMINI contains a mini computer, a proper system shutdown is nesscessary to prevent data corruption. DO NOT simply unplug the power connector. To shut down follow this procedure: Figure 15 1.
5. Install and launch IP Configuration Tool from your computer. This tool is available from the First Access software installation package, but is also available as its own separate installation package which can be downloaded from www.cansec.com/downloads. MAPMINI Page 20 of 28 Installation Manual September 2021 •...
Page 21
Skip step 5 to 11 if static IP address is not required. Figure 17 6. In most cases, the IP Configuration Tool will detect and display the default IP address range ready to be scanned. However, the IP address range can be manually modified accordingly.
Page 22
Figure 20 10. The factory default or current password for a new unconfigured MAPMINI panel is Cansec. The password must be changed to something else other than Cansec. 11. Click Save. The panel saves the new settings and reboots for the settings to take effect.
4. Insert the power connector into the MAPMINI controller. The unit will begin the power up sequence which takes about 30 to 40 seconds. When complete, the MAPMINI controller will emit a series of beeps, 1 beep, 2 beeps or 3 beeps to indicate its provisioned mode First Access, Webster or CloudACS respectively.
Page 24
MAPCFG.txt created by the MAPMINI controller during boot-up sequence. If the file is not present, repeat from step 1. Otherwise proceed to step 7. 7. A similar file will be displayed when opened in Notepad. Figure 22 MAPMINI Page 24 of 28 Installation Manual September 2021 •...
Page 25
Description [USBCFG] [USBCFG] DO NOT Key section – change Password Cansec Factory default password. Please modify to an appropriate password of your choice other than the default password. 10.0.0.101 Factory default IP address. Please Specify the IP address of the host...
Page 26
< USB INIT DONE > < USB INIT DONE > Please remove this line after this file has been correctly modified. The MAPMINI controller reads parameters in this file during boot up sequence and configures the IP address accordingly after which it will write <USB INIT DONE>...
12. If no error file is present, it’s recommended that the file MAPCFG.txt be reviewed to ensure that the line <USB INIT DONE> has been written by the MAPMINI controller indicating that the IP configuration has been successfully saved and initialized.