SmartLock
Controller
®
INSTALLATION MANUAL
November 2018

Advertisement

Table of Contents
loading

Summary of Contents for Cansec SMARTLOCK Series

  • Page 1 SmartLock Controller ® INSTALLATION MANUAL November 2018...
  • Page 2: Table Of Contents

    Table of Contents INTRODUCTION ........................3  Diodes ..........................4  Terminal Strips and Cable ....................5 SPECIFICATIONS ........................6 SMARTLOCK CONTROLLER LAYOUT ................... 8  LED Indicators ........................ 9  Mounting ........................9 RS-485 COMMUNICATIONS WIRING ..................10  CLAUSB Communications Device .................10 ...
  • Page 3 Emergency lockdown functions must operate totally independent of the access control system and must not rely on operation of card readers, access control panels, communications networks, communications devices or host software. Cansec accepts no responsibility for direct or consequential damages resulting from the...
  • Page 4: Introduction

    PC. Up to two control panels are easily mounted in a SmartLock enclosure along with a Cansec 12 VDC power supply and a back-up battery.
  • Page 5: Terminal Strips And Cable

    Complimentary Screwdriver A standard Cansec screwdriver is included with every control panel for use with terminal strips. NOTE: Tech Support will only be provided where product installation guidelines have been followed.
  • Page 6: Specifications

    Specifications Power Requirements  SmartLock ® Controller: ..........12 VDC, 50 mA NOTE: When determining power supply current requirements, you must consider lock and reader current draw if using the same supply for these devices. IMPORTANT: In some jurisdictions, the use of a UL approved power supply and connection to the fire alarm system for emergency release may be required.
  • Page 7 Reader Cable  Wiegand Readers: ....6 conductor (twisted pair not required) ................22 AWG, overall shield ............... 152 m (500 ft) max total length  iButton ® Readers: ............... 6 conductors ............22 AWG, shielded or unshielded ..............15 m (50 ft) max total length Dimensions &...
  • Page 8: Smartlock Controller Layout

    SmartLock Controller Layout EXIT READER (WIEGAND) +12 VDC READER VOLTAGE INPUT SELECTOR ADDRESS ENTRY READER SWITCH DEFAULT (WIEGAND) (DO NOT CHANGE) WIEGAND DATA LED ENTRY READER FIRMWARE CHIP PROGRAMMING MODULE (iBUTTON) RELAY LEDS DOOR CONTACT EXIT BUTTON COMMS DOOR OPERATOR (INPUTS) RS-485 COMMUNICATIONS...
  • Page 9: Led Indicators

    3. The communication LED will flicker GREEN while communicating with SmartLock software. MOUNTING Up to two SmartLock controllers can be mounted in the SmartLock enclosure along with a Cansec 12 VDC power supply and a backup battery. ® SmartLock Controller...
  • Page 10: Rs-485 Communications Wiring

    RS-485 Communications Wiring Up to 30 SmartLock access control panels may be connected on an RS-485 bus. NOTE: For legacy CLA50 and CLAUSB2 communications device wiring please see Appendix section. CLAUSB COMMUNICATIONS DEVICE SMARTLOCK CONTROLLER +12 VDC NOTES: - Each Smartlock controller must ADDRESS “1”...
  • Page 11 CANLAN NETWORK COMMUNICATIONS DEVICE NOTE: The EIA RS-485 standard does not permit T-Tap or Star connections. ® SmartLock Controller Page 11 of 26 Installation Manual Nov 2018 • Rev. 3.2...
  • Page 12: Air-485 Communications Device

    AIR-485 COMMUNICATIONS DEVICE NOTE: The EIA RS-485 standard does not permit T-Tap or Star connections. ® SmartLock Controller Page 12 of 26 Installation Manual Nov 2018 • Rev. 3.2...
  • Page 13: Reader Wiring

    Connecting a 5 V reader to a 12 V power supply will damage the reader. ® NOTE: The SmartLock controller supports Cansec’s 37-bit format as well as standard 26-bit format. ® SmartLock...
  • Page 14: Ibutton ® Reader

    iBUTTON READER ® NOTE: Exit reader not supported with SmartLock iButton readers. NOTE: If using the SmartLock Connect Programming Module with iButton readers, connect the programming module in parallel with the iButton reader. ® SmartLock Controller Page 14 of 26 Installation Manual Nov 2018 •...
  • Page 15: Lock Output Relay Wiring

    Lock Output Relay Wiring DC ELECTRIC STRIKES ≤ 500 mA > 500 mA NOTE: Use 1N400x series diode as shown, to prevent “back EMF” from damaging the controller. ® SmartLock Controller Page 15 of 26 Installation Manual Nov 2018 • Rev. 3.2...
  • Page 16: Dc Maglocks

    DC MAGLOCKS ≤ 500 mA > 500 mA NOTE: Use 1N400x series diode as shown to prevent “back EMF” from damaging the controller if the maglock is not equipped with sufficient spike and surge protection. Check the maglock specifications for details. IMPORTANT: In some jurisdictions, the use of a UL approved power supply and connection to the fire alarm system for emergency release may be required.
  • Page 17: Ac Maglocks And Ac Electric Strikes

    AC MAGLOCKS AND AC ELECTRIC STRIKES IMPORTANT: In some jurisdictions, the use of a UL approved power supply and connection to the fire alarm system for emergency release may be required. Installers should contact the local authority having jurisdiction to verify the specific requirements. Also, a building permit may be required in some jurisdictions for the installation of maglocks.
  • Page 18: Input Wiring

    Input Wiring EXIT BUTTON, HANDICAP BUTTON, DOOR CONTACT IF YOU ARE CONNECTING A DOOR CONTACT SET DIP SWITCH 8 TO OFF (LEFT) IF YOU ARE CONNECTING A DOOR CONTACT SET DIP SWITCH 8 ON (RIGHT) EXIT BUTTON - NORMALLY OPEN - MOMENTARY TO ACTIVATE HANDICAP BUTTON...
  • Page 19: Output Wiring

    Output Wiring DOOR OPERATOR, FORCED ENTRY, DOOR-HELD-OPEN Use dry contact relays. RELAY LEDS TURN SET RELAY CONTACTS ON ACTIVATION = N/O = N/C N/O: RELAY CLOSES ON ACTIVATION N/C: RELAY OPENS ON ACTIVATION DOOR OPERATOR OUTPUT ACTIVATED MOMENTARILY WHEN HANDICAP BUTTON IS DEPRESSED AFTER LOCK RELAY IS ACTIVATED.
  • Page 20: Dip Switch

    DIP Switch FUNCTION The DIP switch is used:  to erase the controller’s memory and run diagnostics  to set the baud rate  to enable or bypass the door contact input  to set the controller address from 1 to 30. LOCATION SWITCH WIEGAND...
  • Page 21: Erase Controller Memory, Diagnostics

    ERASE CONTROLLER MEMORY, DIAGNOSTICS 1. Disconnect communication and device wiring. 2. To erase controller memory (factory default), set all switches to the OFF position (left on diagram above). 3. Disconnect power from the board momentarily then re-connect power. 4. The controller’s memory will be erased. All three relays will cycle ON/OFF once the memory has been cleared.
  • Page 22: Door Contact Bypass Switch Setting

    DOOR CONTACT BYPASS SWITCH SETTING WIEGAND DATA LED IF YOU ARE CONNECTING A DOOR CONTACT SET DIP SWITCH 8 TO OFF (LEFT) IF YOU ARE CONNECTING A DOOR CONTACT SET DIP SWITCH 8 ON (RIGHT) COMMS Door Contact Connected: Set switch 8 OFF (LEFT on diagram) Door Contact Not Connected: Set switch 8 ON (RIGHT on diagram) NOTE: If door contacts are not installed, but door contacts are enabled on the control panel via switch 8, unlock schedules will fail to take effect.
  • Page 23: Controller Address Table

    Controller Address Table Set the unique address of each controller from 0 to 30 as per the table below. The same address used must be programmed in the software in order to establish communications. Switch setting changes do not take effect until the power is disconnected, then reconnected.
  • Page 24 ADDRESS SW-1 SW-2 SW-3 SW-4 SW-5 SW-6 NOTES: 1. Switch setting changes do not take effect until the power is disconnected, then reconnected. ® SmartLock Controller Page 24 of 26 Installation Manual Nov 2018 • Rev. 3.2...
  • Page 25: Appendix

    Appendix CLA50 COMMUNICATIONS WIRING SMARTLOCK +12 VDC CONTROLLER NOTES: - Each Smartlock controller must ADDRESS “1” SHOWN (Dipswitch 1 is OFF) have a unique address - For communication wiring, use 22 AWG, twisted pair, stranded, SMARTLOCK shielded cable, 2000 ft ( 609 m ) MAX CONTROLLER...
  • Page 26 CLAUSB2 COMMUNICATIONS WIRING SmartLock Controller NOTE: The EIA RS-485 standard does not permit T-Tap or Star connections. ® SmartLock is a registered trademark of Cansec Systems Ltd. ® iButton is a registered trademark of Maxim Integrated Products, Inc. ® SmartLock Controller...