Table of contents General Information: Table of contents .................. 3 Features and benefits ................4 Standard unit technical specifications ........... 5 Refrigerant Information ................. 6 Built-in options ..................7 Technical data Dimensions drawings ................8 Performances ..................10 Construction ..................12 Electrical data ..................
General information Features and benefits AEROTOP L is the new air cooled Wide operating range heat pump, equipped with Full DC Outdoor air temperature max / min Inverter technology and R-32 refriger- heating mode < 30 °C / > -14 °C ant, for outdoor installation.
General information Standard unit technical specifications Compressor Range 54–61kW Internal exchanger Refrigeration circuit Inverter controlled rotary-type hermet- Direct expansion heat exchanger, cooling system of the of the electri- ic compressor equipped with a motor brazed AISI 316 stainless steel cal control panel using undercooled protection device for overheating, plates, in pack without seals using...
low toxicity The refrigerant quantity is indicated on the unit plate Quantity factory-loaded refrigerant and equivalent CO2 tons: AEROTOP L Refrigerant (Kg) Equivalent CO tons 54, 61k 65, 79, 88 Physical characteristics of the R32 refrigerant...
General information Built-in options Scope delivery Description User side hydronic group with 1 inverter Hydronic unit made of a centrifugal electric pump, adjusted by way of inverter, body pump and propeller made in AISI 304 steel. The electric pump is equipped with three- phase electric motor with IP55 protection and complete with heat formed insulating casing.
Technical data Dimensions drawings AEROTOP-L 54 - 61 kW 1. Compressor compartment Control keypad Power input Water return 2” Victaulic Water flow 2” Victaulic Pump Functional spaces In modular configuration the water input and output are 4” Victaulic. Lenght 2337 2337 Depth 1130...
Page 9
Technical data Dimensions drawings AEROTOP-L 65 - 88 kW 1. Compressor compartment 2. Electrical panel 3. Control keypad 4. Power input 5. Water return 2” Victaulic 6. Water flow 2” Victaulic 7. Pump 8. Functional spaces In modular configuration the water input and output are 4” Victaulic. Lenght 3190 3190...
Page 11
Technical data Performances The Product is compliant with the ErP (Energy Related Products) European Directive. It includes the Commission delegated Regulation (EU) No 811/2013 (rated heat output ≤ 70 kW at specified reference conditions) and the Commission delegated Regulation (EU) No 813/2013 (rated heat output ≤ 400 kW at specified reference conditions) Contains fluorinated greenhouse gases (GWP 675) 1.
Technical data Construction AEROTOP L Compressor Compressor type ROTARY INVERTER SCROLL INVERTER Refrigerant N° compressor Oil charge Refrigerant charge 15,0 15,0 21,0 21,0 21,0 N° circuits User side exchanger Type of internal exchanger BPHE Water content External Section Fans Fans type BRUSHLESS DC MOTOR N°...
46,0 60,2 60,2 60,2 Power supply 400/3/50 (+ NEUTRAL) +/- 10%. Maximum Phase Unbalance: 2%. For non standard voltage please contact ELCO technical office Wiring cross sections and fuse protection Remote ON - OFF External power supply AEROTOP L Wiring...
Technical data Sound levels Standard mode Sound power level Sound pressure Sound power level level AEROTOP L Octave band (Hz) 1000 2000 4000 8000 dB(A) dB(A) Silenced Mode Sound power level Sound pressure Sound power level level AEROTOP L Octave band (Hz)
Sound levels Performance correction factors At maximum conditions data Sound power level Sound Sound pressurelevel power level AEROTOP L Octave band (Hz) 1000 2000 4000 8000 dB(A) dB(A) Sound levels refer to units with maximum test conditions. The sound pressure level refers to a distance of 1 meter from the outer surface of the unit operating in open field.
Technical data Fouling and glycol use correction factors, overload and control device Correction factors for Glycol use % ethylene glycol by weight Freezing point °C Correction factor for unit cooling capacity 0,984 0,973 0,965 0,96 0,95 Correction factor for flow rate 1,019 1,051 1,092...
Outdoor air temperature Tae (°C) sulting in damages to the heat pump in addition to a drop in performance. Twu [°C] = Leaving exchanger water Operating range - Heating - AEROTOP L 54 - 61kW temperature Tae [°C] = External exchanger return air temperature...
To the internal exchanger pressure drops must be added the pressure drops of the steel mesh mechanical filter that must be placed on the water input line. It is a device compulsory for the correct unit operation, and it is provided by ELCO as accesso- Admissible water flow rates Min.
During the installation phase it is possible to choose the most suitable head curve for system requirements by setting the inverter frequency. The pump will always work at fixed flow. Water fittings are Victaulic type by 2 Pump available pressure AEROTOP L 54 – 61 kW Caution: in order to obtain useful head values, the head represented in these diagrams must be lowered by: ...
Page 20
Hydronic assembly Unit with 1 Inverter pump Pump available pressure AEROTOP L 65 – 88 kW Caution: in order to obtain useful head values, the head represented in these diagrams must be lowered by: Condenser pressure drops IFWX - Steel mesh strainer on the water side”...
Installation General notes Safety areas and functional distances Positioning Installation criteria: Structure for installation. Consider these elements during posi- Customer approval Both steel and concrete bases may tioning: position accessible safely be suitable. Technical spaces requested by the ...
D = 500 mm E = 6000 Do not smoke or use open flames within this area F = 500 mm G = 500 mm Anti-vibration mounts Option AEROTOP L 54 - 61 65 - 88 support points Configuration standard standard...
Installation Water quality Water quality New systems Risk of frost In case of new installations, it is es- When the outside temperature gets Circulators function well exclusively sential to wash the entire installation close to 0°C, the water in the pipes with clean and high-quality tap water.
External air sensor For systems that deviate from the Electric heating element standards, an electrical diagram is Buffer reversing valve required. This can be obtained from ELCO as a service. Secondary heating circuit HC1) Shut-off valve NRV Non-return valve Expansion valve...
Page 37
For systems that deviate from the Buffer tank sensor bottom standards, an electrical diagram is External air sensor required. This can be obtained from ELCO as a service. Secondary heating circuit HC1 Secondary heating circuit HC2 Mixing valve HC1 Mixing valve HC2...
Page 38
For systems that deviate from the Flow sensor HC2 standards, an electrical diagram is HP Return sensor required. This can be obtained from ELCO as a service. Electric heating element Secondary heating circuit HC1 Shut-off valve NRV Non-return valve Expansion valve...
Page 39
For systems that deviate from the Flow sensor HC2 standards, an electrical diagram is HP Return sensor required. This can be obtained from ELCO as a service. DHW Sensor top Electric heating element Electric heating element Secondary heating circuit HC1...
System configurations Electric connection Remote On - Off Heat - Cool Signals Anti-snow function Domestic hot water Antifreeze heater...
Page 41
System configurations Electric connection Remote Interface Modul Port Definition CN5: SA 5 C/H Voltage free digital input The module has five digital inputs with HMI side: optocouplers and an isolated BMS CN1: A, B CN6: SA 6 DHW Voltage free digital input Modbus RTU port with variable baud power supply 7-17Vac/dc rate.
System configurations Cascade management Cascade management Modular system connection diagram - addressing It is possible to connect up to 16 units on a local network, reaching a maxi- mum power of 1400 kW and up to 4 units connected hydraulically. The com- binations can also occur with units with different power.
System configurations Modular configuration units Modular system configuration Modular system connection diagram Management of the entire system Clearance values takes place through a unit defined as Power supply master. The master unit controller can Connection be set up remotely at a maximum distance of up to 300 m.
If the system is satisfied (unit off): When the temperature probe (T5), sup- * Accessory plied by ELCO and positioned inside the storage calls for production of DHW, the unit dedicated to DHW activates, changing the set-point from set system...
Page 48
Service: UK Importer ELCO HEATING SOLUTION LIMITED 3 Juniper West, Fenton Way Basildon, SS15 6SJ ELCO GmbH Hohenzollernstraße 31 D - 72379 Hechingen www.elco.net...