Page 1
P.O. Box 400 • Cordele, Georgia 31010 • 156 Seedling Drive • Cordele, Georgia 31015 (229) 273-3636 • Fax (229) 273-5154 E-mail: marvairsales@airxcel.com • Internet: www.Marvair.com The most current version of this manual can be found at www.Marvair.com. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Page 2
How To Use This Manual This manual is intended to be a comprehensive guide to the installation of the Eubank EAA family of vertical packaged ® heat pumps. It contains installation, troubleshooting, maintenance, warranty, and application information. The information contained in this manual is to be used by the installer as a guide only. This manual does not supersede or circumvent any applicable national or local codes.
All internal wiring is complete. Eubank EAA heat pump models are available in a wide variety of styles and configurations to meet the various ventilation and cooling requirements. For school classrooms, models are available to comply with the ASHRAE 62-1999 standard, “Ventilation for Acceptable Indoor Air Quality.”...
30 Special Variation $ = Special Configuration Not Covered by Model Nomenclature Note: Not all options are available with all configurations. Contact your Eubank sales representative for configuration details and feature compatibility. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
1.5 General Operation Refrigerant Cycle Eubank heat pumps use R-410A refrigerant in a conventional vapor-compression refrigeration cycle to transfer heat. In the cooling mode, a double blower assembly blows indoor air across the evaporator (indoor coil). Liquid refrigerant passing through the evaporator is boiled into gas by heat removed from the air.
Page 8
HVAC is in economizer mode verses mechanical cooling mode. This feedback allows the CommStat 4 to initiate the forced cooling feature to override economizer cooling and force mechanical cooling. When used with minimum position potentiometer (optional), the Eubank economizer can meet requirements of ASHRAE Std. 62.
The heat pump is factory wired to be normally open. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Page 10
Electric Heat During Defrost (EHDD) and “No” selected for the S-Circuit, the electric heat (EH) output will be energized during a defrost cycle to supply heat while the coil defrosts. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Page 11
LPS fault, and initiate the 3 minute anti-short cycle timer. If two LPS faults occur within a one hour period, the control will enter a LPS lockout condition Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Page 12
HPS High Pressure switch terminals are the high pressure switch input. LPS Loss of Charge switch terminals are the loss of charge switch input. DS The DS terminals are the defrost sensor input. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Adjustable Outdoor Thermostat Will not allow electric resistance heat to be energized unless the outdoor temperature is below the desired set point. Field or factory installed. Available on all Eubank units. P/N 93934 Single Point Feed When multiple internal disconnects are used, single point feed permits only one field power supply to heat pump.
(i.e., economizer cooling). If the outdoor ambient is too hot or humid, the sensor will place the actuator in the closed or minimum open position and activate mechanical cooling. The compressor is locked out during the economizer cooling mode. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
The thermistor senses the air temperature entering the structure, and provides a signal to the economizer controller for modulating the position of the damper. Nominal resistance of the sensor at 77°F is 3000 ohms. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
C) The unit exhausts air. Be sure that the airflow is not impeded by shrubbery or other obstructions. D) When installing multiple units, please note the recommended clearances noted in Table 4. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
2.3 Installation Materials Installation Kits Eubank EAA Heat Pumps have built-in mounting flanges that function as side brackets. All models require and are shipped with a bottom mounting bracket. On units with the "N" ventilation option, there is a fresh air hood factory installed behind the lower front panel.
Page 18
1” (25mm) thick filter. The return filter grille is not recommended for use with the EAA heat pumps with economizers. Additional Items Needed: Additional hardware and miscellaneous supplies (not furnished by Eubank ) are needed for installation. ®...
Applications using duct work should be designed and installed in accordance with all applicable safety codes and standards. Eubank strongly recommends referring to the current edition of the National Fire Protection Association Standards 90A and 90B before designing and installing duct work. The duct system must be engineered to insure sufficient air flow through the unit to prevent over-heating of the heater element.
For example, on wooden structures, use 3/8 x 2-1/2 inch all-thread lag screws. The screws must penetrate the center of the wall stud. Drill a pilot hole in the stud to prevent it from splitting. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
10. To minimize sound transmission, a latex based, insulating foam seal may be applied between the duct extensions and the frame for the wall openings. NOTE: DO NOT USE THE FOAM ON ANY UNITS WITH ELECTRIC RESISTANT HEATERS. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
An alternate method of verification for self contained system with small Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Page 23
Terminals 8 & 10 on the Eubank with economizer can be connected to a normally closed smoke alarm or fire stat to cause equipment shutdown when the circuit is opened. (Remove factory jumper).
Various thermostats can be used to control the heat pump. The thermostat may have a fan switch with an Automatic and On positions, a system switch with Heat, Cool, and Off positions, and an emergency heat position with lights. The spec sheets have detailed description of the various Eubank ®...
2. Raise the heating set point temperature to a setting which is higher than the room temperature. The fan and compressor should cycle on after time delay (standard on Eubank heat pumps with an economizer and optional on all other Eubank units) has cycled.
68ºF and no higher than 78ºF. Allow the refrigerant system to stabilize for at least five minutes and adjust the temperature as desired. Adjustment Knob Positive (Red) Negative (Black) Figure 7 - Desired Temperature Set Point Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
3.4 Ventilation System Set-Up: Manual Fresh Air System (Configuration N). This is the standard ventilation system in Eubank heat pumps. Fresh air ventilation by means of a damper can provide up to 15% of rated air flow of outside air. The damper has four positions corresponding to 0, 5, 10 and 15% of rated air flow of outside air.
The motorized damper, Configuration B, can be controlled by an optional relay that allows additional external control with a choice of 24, 120 or 240V coils to regulate fresh air ventilation in response to a control located remote from the Eubank heat pump. Eubank Wall Mount Heat Pump I&O Manual...
Please read the Chapter 1 for basic information about the unit. Eubank Heat Pumps are thoroughly tested before they are shipped from the factory. However, it is possible that a defect may escape undetected, or damage may have occurred during transportation. However, the great majority of problems result from installation errors.
Test components (especially the compressor) for shorts. 4. Excessively high or low supply volt- 4. Note voltage range limitations specific to the age or phase loss (3ø only). compressor troubleshooting section. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
A short circuit at a high voltages indicates a motor defect. Do not do this test under vacuum. 4. On single phase models, check the capacitor by substitution. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
The indoor evaporator fan motor is cycled by the blower timed delay relay. See Figure 9. Due to the large number of variations and options available for the Eubank heat pumps, it is not practical to include every possible wiring schematic in this manual. The following schematics are typical. Included in each heat pump is the electrical schematic for that unit.
Regularly check the primary and secondary condensate drains. The secondary drain has a stand pipe. An obstruction will force water to dump into the middle of the unit and drain out the sides of the Eubank Heat Pump, causing discoloration of the side panels. If discoloration is noted, service the drains.
Marvair, ICE, Eubank Products 90 Days w/Flat Rate Labor (See Marvair, ICE, Eubank Flat Rate Labor Guidelines) 1 Year Parts 5 Years Compressor If any part of your Marvair, Inc. unit fails within 90 days of the commencement of the warranty, Marvair, Inc. will furnish without charge, EX Works, Cordele, Georgia, the required replacement part and pay for the labor to replace the part in accordance with the Marvair, Inc.
The 1" (25.4 mm) clearance must extend on all sides of the supply duct for the first 3 feet (1 meter) from the unit. IMPORTANT: Eubank requires a minimum of 1" (25.4 mm) from the surface of any supply ducts to combustible material for the first 3 feet (1 meter) of the duct.
Page 41
15. Place the wiring diagram provided with the heater kit inside the zip lock bag which is affixed to the back side of the control box cover. 16. Replace the control box cover, the bottom front cover and the top front panel. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Is the correct filter(s) in place and clean? ................. ❒Yes ❒No Refrigerant Piping Is there any evidence of refrigerant leaks (oil leaks, etc.)? ..........❒Yes ❒No If leaks are found, report them to Eubank Warranty Service Dept. Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Page 44
If using a standard thermostat, Set the Control to ON, Mode to Cooling, Fan to Auto (other controls, set appropriately for cooling mode). Note: The reversing valve (Eubank Heat Pumps) is energized for “Cooling”. The “O” signal from the thermostat is Required.
Page 45
719 / 3 = 239.7 Volts (Average Voltage) 239.7 (Average Voltage) – 235 (Maximum Deviation) = 4.7 (Deviation Difference) (4.7 x 100)/239.7 = 1.95% Voltage Imbalance (Less than 2% is acceptable) Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Page 46
Is the Compressor On? ...................... ❒Yes ❒No Is the Condenser Fan (CFM) On? ..................❒Yes ❒No Is the Heater Off? (Clamp an AmpProbe on one leg of the heater contactor to verify) ... ❒Yes ❒No Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Page 47
Return Air Temperature (RAT) wb (used to calculate RH% of Return Air) ºF Supply Air Temperature (SAT) db (Acceptable Range 55ºF (+/- 3ºF) ºF Return Air Temperature (SAT) wb (used to calculate RH% of Supply Air) ºF Eubank Wall Mount Heat Pump I&O Manual 11/2021 New...
Page 48
If using a standard thermostat, Set the Control to ON, Mode to Heat, Fan to Auto (other controls, set appropriately for heating mode). Note: The reversing valve (Eubank Heat Pumps) is de-energized for “Cooling”. The “O” signal from the thermostat is Not Required.
Page 49
Mechanical Heat Lockout, start heating with Only Electric heat. Notice: system did not turn off. “Mechanical Heat” turned Off and “Electric Heat” turned On. Note: The “S” Circuit (Eubank Heat Pump control board) must be set to “Yes”, to allow Mechanical Heat Lockout.
Page 50
** Please provide a description of the issue in the Notes section below and if you need help, call: Eubank Technical and Warranty Support: (888) 726-2734 This number is manned M-F, 8:00am to 5:00pm eastern. Technical support calls will be returned M-F, 5:00pm to 8:00pm eastern.
Need help?
Do you have a question about the EAA1042H and is the answer not in the manual?
Questions and answers