Service Life Graph; Order Reference - Pilz PNOZ X9 Operating Manual

Safety relays
Hide thumbs Also See for PNOZ X9:
Table of Contents

Advertisement

PNOZ X9

Service life graph

The service life graphs indicate the number of cycles from which failures due to wear must
be expected. The wear is mainly caused by the electrical load; the mechanical load is negli-
gible.
Example
}
Inductive load: 0.2 A
}
Utilisation category: AC15
}
Contact service life: 4 000 000 cycles
Provided the application to be implemented requires fewer than 4 000 000 cycles, the PFH
value (see Technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With DC con-
tactors, use flywheel diodes for spark suppression.

Order reference

Product type
PNOZ X9
PNOZ X9
PNOZ X9
Operating Manual PNOZ X9
19526-EN-10
Switching current (A)
Features
24 VAC; 24 VDC
100 - 120 V AC; 24 V DC
200 - 230 V AC; 24 V DC
Connection type
Screw terminals
Screw terminals
Screw terminals
Order no.
774609
774605
774606
| 24