Preparing For Operation - Pilz PNOZ X9 Operating Manual

Safety relays
Hide thumbs Also See for PNOZ X9:
Table of Contents

Advertisement

PNOZ X9
Important for detection of shorts across contacts:
As this function for detecting shorts across contacts is not failsafe, it is tested by Pilz during
the final control check. If there is a danger of exceeding the cable runs, we recommend the
following test after the installation of the device:
1. Unit ready for operation (output contacts closed)
2. Short circuit the test terminals S12, S22 for detecting shorts across the inputs.
3. The unit's fuse must be triggered and the output contacts must open. Cable lengths in
the scale of the maximum length can delay the fuse triggering for up to 2 minutes.
4. Reset the fuse: remove the short circuit and switch off the supply voltage for approx. 1
minute.

Preparing for operation

Supply voltage
Input circuit
E-STOP
without detection of shorts across
contacts
E-STOP
with detection of shorts across
contacts
Safety gate
without detection of shorts across
contacts
Safety gate
with detection of shorts across
contacts
Operating Manual PNOZ X9
19526-EN-10
AC
A1
A2
Single-channel
S11
S21
S12
S22
S52
S11
S21
S12
S22
S52
DC
L1
N
FE
Dual-channel
S1
S21
S22
S11
S52
S1
S21
S22
B1
L+
B2
L-
S1
S11
S12
S52
S1
S11
S21
S22
S12
S11
S1
S2
S12
S52