  • ENGLISH, page 53
8.3.9
A-label pump LED flashes intermittently red/green
Possible causes:
Too high or too low mains voltage.
No È
Pump temperature is too high.
8.3.10 A-label pump LED flashes red
Possible causes:
Pump stopped.
Solution:
Yes Æ Check the mains voltage.
Yes Æ Check the water and ambient temperature.
Solution:
Reset the pump by switching off the unit by pressing the on/off button for at least 20
seconds
(attention: if the pump has been set to continuous, the pump can only
Yes Æ
be reset by pulling the plug from the socket).
Replace the pump.
47