Accessory - Riello RL 55/M BLU Installation, Use And Maintenance Instructions

Oil burners
Table of Contents

Advertisement

ACCESSORIES (optional):
• OUTPUT MODULATION REGULATOR KIT
Two components should be ordered:
• output regulator to install on the burner;
• probe to install on the boiler.
PARAMETER TO BE CHECKED
Temperature
Pressure
• DEGASSING UNIT
It may occur that a certain amount of air is contained in the light oil sucked up by the pump. This air may originate from the light oil itself as a
consequence of depressurization or air leaking past imperfect seals.
In double-pipe systems, the air returns to the tank from the return pipe; in single-pipe systems, the air remains in circulation causing pressure var-
iations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the burner in single-pipe installations.
Degassing units are provided in two versions:
CODE 3010054 without filter
CODE 3010055 with filter
- Burner delivery
- Light oil pressure
- Ambient temperature
- Ambient temperature
- Light oil temperature
- Light oil temperature
- Attachment connectors
For burner deliveries higher than 80 kg/h, install two parallel degassing units.
Range
- 100...+ 500 °C
0...2,5 bar
0...16 bar
: max. 80 kg/h
: max. 0.7 bar
: max. 50 °C (without filter)
: max. 40 °C (with filter)
: max. 50 °C (without filter)
: max. 40 °C (with filter)
: 1/4 inch
PROBE
Type
Code
PT 100
3010110
Probe with output
3010213
4...20 mA
3010214
37
POWER REGULATOR
Type
Code
RWF40
3010212