CONTENTS GUARANTEE AND RESPONSIBILITY The manufacturer guarantees its new products from the installation date, in accordance with the regulations in force and/or the sales con- TECHNICAL DATA......page 3 tract.
(2) Sound pressure measured in manufacturers combustion laboratory, with burner operating on test boiler and at maximum rated output. (3) Equivalent Btu values based on 1 USGPH = 140,000 Btu/hr. Burner models designations MODEL RIELLO CODE RBNA CODE VOLTAGE FLAME SAFEGUARD...
BURNER DESCRIPTION (A) 1 Ignition electrodes 2 Combustion head 3 Screw for combustion head adjustment 4 Flame sensor for flame monitoring 5 Screw for fixing fan to flange 6 Slide bars for opening the burner and inspecting the combustion head 7 Hydraulic cylinder for regulation of the air damper in low and high fire positions.
FIRING RATE (A) The RL 28/2 - 38/2 - 50/2 Model burners are available in low-high firing configuration. LOW FIRE DELIVERY must be selected within area A of the adjacent diagrams. HIGH FIRE DELIVERY must be selected within area B. This area provides the maximum delivery of the burner in relation to the pressure in the combustion chamber.
INSTALLATION All the installation, maintenance and disassembly operations must be carried inch with electricity supply disconnected. DANGER RL 28/2 “ “ 5 / 16 13 / 16 3 / 8 The installation of the burner must be RL 38/2 “ “...
D458 year during regular maintenance operations. Caution: The use of nozzles other than those specified by Riello S.p.A. and inadequate regular maintenance may result into emission limits non- conforming to the values set forth by the regulations in force, and in extremely serious cases, into potential hazards to people and objects.
HYDRAULIC SYSTEM FUEL SUPPLY DOUBLE - PIPE SYSTEM (A) The burner is equipped with a self-priming pump which is capable of feeding itself within the limits listed in the table at the left. The tank higher than the burner A The distance "P"...
BURNER CALIBRATION All the installation, maintenance and disassembly operations must be carried with electricity supply disconnected. DANGER The installation of the burner must be carried out by qualified personnel, as indicated in this manual and in compliance with the standards and regulations of the WARNING laws in force.
FINAL CHECKS • Obscure the flame sensor and switch on the burner: the burner should start and then lock-out about 5 s af- ter opening of the low fire nozzle valve. • Illuminate the flame sensor and reset the burner: the burner should go into lock-out .
BURNER OPERATION BURNER STARTING (A) Operating control closes. The motor starts and the ignition transformer is con- nected. The pump 3) sucks the fuel from the tank through the piping 1) and the filter 2) and pumps it under pressure for delivery.
The electrical wirings must be carried out in conformity with the regulations in force in the countries of destination, and by qualified personnel. Riello S.p.A. cannot accept any responsibility for modifications or connections other than those shown in these diagrams. IMPORTANT The burner is factory set for low - high operation and it must be connected to the OCR control device to control fuel oil valve V2.
Page 20
Key to Layouts + BB - Components on board burners + BQ - Components on board main panel + BC - Components on board boller DISC1 - Disconnect switch motor DISC2 - Disconnect switch auxiliary - Motor fuse - Auxiliary fuse - High limit control - Control box - Remote lock-out signal...
Burner firing rates according to air density CORRECTION FACTOR average barom. above sea level Air temperature pressure °F (°C) “ W.C. mbar 0 (0°C) 41 (5°C) 50 (10°C) 59 (15°C) 68 (20°C) 77 (25°C) 86 (30°C) 104 (40°F) 1013 1,087 1,068 1,049 1,031...
Page 22
OPERATION LAYOUT Low-High Switching times are given in seconds, in the burner startup sequence. LAL 2.25 optional optional Legend for the times Pre-purge time with air damper open. Safety time. Pre-ignition time, short (“Z” connected terminal “16”). Interval between voltage at terminals “18” and “20” Air damper running time to OPEN position.
Page 23
BURNER FAULT INDICATIONS Control program fault conditions and lock-out indication Whenever a fault occurs, the sequence switch stops and with it the lock-out indicator. The symbol above the reading mark of the indicator gives the type of fault: No start One of the contacts has not closed The contact of the limit thermostat or any other switching devices in the control loop of terminal 4 to terminal 5 are...
Appendix - Spare parts Appendix - Spare parts 2915758...
Page 25
Appendix - Spare parts COD. DESCRIPTION BURNER SERIAL NUMBER • • • • • • • 3005733 VALVE • • • • • • • 3007077 SEAL • • • • • • • 3006719 CONNECTOR • • • • • • • 3007079 SEAL •...
Page 26
Appendix - Spare parts COD. DESCRIPTION BURNER SERIAL NUMBER • • • • • • 3003783 SUPPORT • 3013876 SUPPORT • • • • • • C5360001 3012950 CONTROL BOX BASE • • • • • • • 3012938 TRANSFORMER •...
Page 27
Appendix - Spare parts COD. DESCRIPTION BURNER SERIAL NUMBER • • • • • • • 3003826 AIR DAMPER ASSEMBLY ADVISED PARTS Spare parts for minimum fittings Spare parts for basic safety fittings A+B+C = Spare parts for extended safety fittings 2915758...
Page 28
Appendix - Burner start up report Appendix - Burner start up report Model number: Serial number: Project name: Start-up date: Installing contractor: Phone number: OIL OPERATION : Low Fire Oil supply pressure: High Fire : Low Fire Oil suction pressure: High Fire Control Power Supply: CO: Low Fire...
Page 32