Installation, use and maintenance instructions
Light oil burners
GB
Low - High two stage operation
C9511200
C9511220
20166332
C9512200
C9512220
20166333
C9512210
C9512250
C9512251
C9513200
C9513201
C9513210
C9513203
C9513253
CODE
MODEL
RL 28/2
RL 28/2
RL 28/2
RL 38/2
RL 38/2
RL 38/2
RL 38/2
RL 38/2
RL 38/2
RL 50/2
RL 50/2
RL 50/2
RL 50/2
RL 50/2
2915758 (5) - 06/2021

Advertisement

Table of Contents
loading

Summary of Contents for Riello C9511200

  • Page 1 Installation, use and maintenance instructions Light oil burners Low - High two stage operation CODE MODEL C9511200 RL 28/2 C9511220 RL 28/2 20166332 RL 28/2 C9512200 RL 38/2 C9512220 RL 38/2 20166333 RL 38/2 C9512210 RL 38/2 C9512250 RL 38/2...
  • Page 2 Original instructions...
  • Page 3: Table Of Contents

    CONTENTS GUARANTEE AND RESPONSIBILITY The manufacturer guarantees its new products from the installation date, in accordance with the regulations in force and/or the sales con- TECHNICAL DATA......page 3 tract.
  • Page 4: Technical Data

    (2) Sound pressure measured in manufacturers combustion laboratory, with burner operating on test boiler and at maximum rated output. (3) Equivalent Btu values based on 1 USGPH = 140,000 Btu/hr. Burner models designations MODEL RIELLO CODE RBNA CODE VOLTAGE FLAME SAFEGUARD...
  • Page 5: Burner Description

    BURNER DESCRIPTION (A) 1 Ignition electrodes 2 Combustion head 3 Screw for combustion head adjustment 4 Flame sensor for flame monitoring 5 Screw for fixing fan to flange 6 Slide bars for opening the burner and inspecting the combustion head 7 Hydraulic cylinder for regulation of the air damper in low and high fire positions.
  • Page 6: Firing Rate

    FIRING RATE (A) The RL 28/2 - 38/2 - 50/2 Model burners are available in low-high firing configuration. LOW FIRE DELIVERY must be selected within area A of the adjacent diagrams. HIGH FIRE DELIVERY must be selected within area B. This area provides the maximum delivery of the burner in relation to the pressure in the combustion chamber.
  • Page 7: Installation

    INSTALLATION All the installation, maintenance and disassembly operations must be carried inch with electricity supply disconnected. DANGER RL 28/2 “ “ 5 / 16 13 / 16 3 / 8 The installation of the burner must be RL 38/2 “ “...
  • Page 8: Nozzle Assembly

    D458 year during regular maintenance operations. Caution: The use of nozzles other than those specified by Riello S.p.A. and inadequate regular maintenance may result into emission limits non- conforming to the values set forth by the regulations in force, and in extremely serious cases, into potential hazards to people and objects.
  • Page 9: Fuel Supply

    HYDRAULIC SYSTEM FUEL SUPPLY DOUBLE - PIPE SYSTEM (A) The burner is equipped with a self-priming pump which is capable of feeding itself within the limits listed in the table at the left. The tank higher than the burner A The distance "P"...
  • Page 10: Pump

    PUMP (A) 1 - Suction 1/4” NPT 2 - Return 1/4” NPT 3 - Pressure gauge attachment G 1/8 4 - Vacuum gauge attachment G 1/8 5 - Pressure adjustment screw A - Min. delivery rate at 174 PSI pressure D2286 B - Delivery pressure range C - Max.
  • Page 11: Burner Calibration

    BURNER CALIBRATION All the installation, maintenance and disassembly operations must be carried with electricity supply disconnected. DANGER The installation of the burner must be carried out by qualified personnel, as indicated in this manual and in compliance with the standards and regulations of the WARNING laws in force.
  • Page 12: Final Check

    FINAL CHECKS • Obscure the flame sensor and switch on the burner: the burner should start and then lock-out about 5 s af- ter opening of the low fire nozzle valve. • Illuminate the flame sensor and reset the burner: the burner should go into lock-out .
  • Page 13: Burner Operation

    BURNER OPERATION BURNER STARTING (A) Operating control closes. The motor starts and the ignition transformer is con- nected. The pump 3) sucks the fuel from the tank through the piping 1) and the filter 2) and pumps it under pressure for delivery.
  • Page 14: Appendix

    The electrical wirings must be carried out in conformity with the regulations in force in the countries of destination, and by qualified personnel. Riello S.p.A. cannot accept any responsibility for modifications or connections other than those shown in these diagrams. IMPORTANT The burner is factory set for low - high operation and it must be connected to the OCR control device to control fuel oil valve V2.
  • Page 15: Switchboard Layout

    156)-4 6# *74-4 ,15+ 156)-4 64 " " " +76*74-4 " 7+*74-4 " 6$ +).40-)6 & 156)-4 & ,15+ " +4 " " > 6& 6& " 6" " 56)/- !" & 5 & !& +)61 7-5560-4915-56)6-, )914-5)4- &)9/6-9 # **=? //HAA 4,4A@...
  • Page 16 RL 50/2 SINGLE PHASE...
  • Page 17 +61775.)2-4)61 +D=CAJDAMEHA?A?JEBHJAHE=%JJAHE=B?JH>N  ! ! ! " " ! ! !  5 & & 55 & " 6! *" *"  56)/- 25+4 " !" & !& +)61 7-5560-4915-56)6-, )914-5)4-&)9/6-9# **=? //HAA 4,4A@ RL 28/2 - 38/2 - 50/2 SINGLE PHASE 50--6 **HM /;/HAO...
  • Page 18 156)-4 6# *74-4 6* ,15+  .7 156)-4 *3  64 6* " " " " +76*74-4   5-6)6  " 7+*74-4 " 6$ +).40-)6 & 156)-4  & 6* ,15+ " +4 " " > 6& 6& " 6"...
  • Page 19  +61775.)2-4)61 +D=CAJDAMEHA?A?JEBHJAHE=%JJAHE=B?JH>N  ! ! ! " "  ! ! !  5 & & 55 & " 6! *" *"  56)/- 25+4 " !" & !& +)61 7-5560-4915-56)6-, )914-5)4-&)9/6-9# **=? //HAA 4,4A@ RL 38/2 - 50/2 THREE PHASE 50--6 **HM /;/HAO...
  • Page 20 Key to Layouts + BB - Components on board burners + BQ - Components on board main panel + BC - Components on board boller DISC1 - Disconnect switch motor DISC2 - Disconnect switch auxiliary - Motor fuse - Auxiliary fuse - High limit control - Control box - Remote lock-out signal...
  • Page 21: Burner Firing Rates According To Air Density

    Burner firing rates according to air density CORRECTION FACTOR average barom. above sea level Air temperature pressure °F (°C) “ W.C. mbar 0 (0°C) 41 (5°C) 50 (10°C) 59 (15°C) 68 (20°C) 77 (25°C) 86 (30°C) 104 (40°F) 1013 1,087 1,068 1,049 1,031...
  • Page 22 OPERATION LAYOUT Low-High Switching times are given in seconds, in the burner startup sequence. LAL 2.25 optional optional Legend for the times Pre-purge time with air damper open. Safety time. Pre-ignition time, short (“Z” connected terminal “16”). Interval between voltage at terminals “18” and “20” Air damper running time to OPEN position.
  • Page 23 BURNER FAULT INDICATIONS Control program fault conditions and lock-out indication Whenever a fault occurs, the sequence switch stops and with it the lock-out indicator. The symbol above the reading mark of the indicator gives the type of fault: No start One of the contacts has not closed The contact of the limit thermostat or any other switching devices in the control loop of terminal 4 to terminal 5 are...
  • Page 24: Start Up Report

    Appendix - Spare parts Appendix - Spare parts 2915758...
  • Page 25 Appendix - Spare parts COD. DESCRIPTION BURNER SERIAL NUMBER • • • • • • • 3005733 VALVE • • • • • • • 3007077 SEAL • • • • • • • 3006719 CONNECTOR • • • • • • • 3007079 SEAL •...
  • Page 26 Appendix - Spare parts COD. DESCRIPTION BURNER SERIAL NUMBER • • • • • • 3003783 SUPPORT • 3013876 SUPPORT • • • • • • C5360001 3012950 CONTROL BOX BASE • • • • • • • 3012938 TRANSFORMER •...
  • Page 27 Appendix - Spare parts COD. DESCRIPTION BURNER SERIAL NUMBER • • • • • • • 3003826 AIR DAMPER ASSEMBLY ADVISED PARTS Spare parts for minimum fittings Spare parts for basic safety fittings A+B+C = Spare parts for extended safety fittings 2915758...
  • Page 28 Appendix - Burner start up report Appendix - Burner start up report Model number: Serial number: Project name: Start-up date: Installing contractor: Phone number: OIL OPERATION : Low Fire Oil supply pressure: High Fire : Low Fire Oil suction pressure: High Fire Control Power Supply: CO: Low Fire...
  • Page 32 RIELLO S.p.A. I-37045 Legnago (VR) Tel.: +39.0442.630111 http:// www.riello.com RIELLO BURNERS NORTH AMERICA http://www.riello.ca 35 Pond Park Road 2165 Meadowpine Blvd Hingham, Massachusetts, Mississauga, Ontario U.S.A. 02043 1-800-4-RIELLO Canada L5N 6H6 Subject to modifications...